ELE03-01685
| ELE-Aging Inspection | 4/13/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | | NH |
|
|
could not get access even after talked to contractor and expired per J Schmer 4/13/2004 2:16:09 PM 4/13/2004 2:16:36 PM
|
ELE03-02689
| ELE-Aging Inspection | 4/13/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | | PASS |
|
|
|
ELE04-00222
| Final | 4/12/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | A | PASS |
|
|
ed; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
ELE04-01000
| Temporary Service | 4/12/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | A | FAIL |
|
|
temp pole on north west corner of lot by petra job trailer; Phone #: ###-#### Internet Inspection Request from: Rich Rice
GFCi protect 240v receps.
ground job trailer.
drive ground rods flush.
ground wireway/gutter.
LFMC requires grounding wire to be installed and bond bushing between meter and main. 4/13/2004 9:20:08 AM
|
ELE03-00520
| Final | 4/12/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | A | PASS |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
ELE04-00990
| Conference | 4/12/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | A | PART |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
ELE04-00978
| Permanent Service | 4/12/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | A | PASS |
|
|
mr lemmon; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
P/S O/H N Ok 4/13/2004 10:25:11 AM
|
ELE04-01031
| Permanent Service | 4/13/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | P | FAIL |
|
|
###-#### glenn
cannot have 2 services to a building
conductors for street lights cannot enter the building 4/13/2004 3:36:53 PM
|
ELE04-01032
| Electrical Rough-In | 4/13/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | P | FAIL |
|
|
###-#### james
4 violations in one box.
box overfill.
screws inside box.
parallel romex not protected within 1 1/4 in.
romex not supported within 8 in. in several places.
address is west north mountain not north 4/13/2004 1:50:31 PM
|
ELE04-00375
| Electrical Rough-In | 4/13/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | P | PASS |
|
|
LLOYD; Phone #: ###-#### Internet Inspection Request from: Darla Downs
|
ELE04-00375
| Final | 4/13/2004 | 4/13/2004 | 4/13/2004 12:00:00 AM | P | PART |
|
|
LLOYD; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ok except for two sound rooms 4/13/2004 2:12:55 PM
|