Inspections for the day of: Tuesday, April 13, 2004.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-01685 ELE-Aging Inspection4/13/20044/13/20044/13/2004 12:00:00 AM NH
could not get access even after talked to contractor and expired per J Schmer 4/13/2004 2:16:09 PM 4/13/2004 2:16:36 PM
ELE03-02689 ELE-Aging Inspection4/13/20044/13/20044/13/2004 12:00:00 AM PASS
ELE04-00222 Final4/12/20044/13/20044/13/2004 12:00:00 AMAPASS
ed; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ELE04-01000 Temporary Service4/12/20044/13/20044/13/2004 12:00:00 AMAFAIL
temp pole on north west corner of lot by petra job trailer; Phone #: ###-#### Internet Inspection Request from: Rich Rice
GFCi protect 240v receps.
ground job trailer.
drive ground rods flush.
ground wireway/gutter.
LFMC requires grounding wire to be installed and bond bushing between meter and main. 4/13/2004 9:20:08 AM
ELE03-00520 Final4/12/20044/13/20044/13/2004 12:00:00 AMAPASS
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
ELE04-00990 Conference4/12/20044/13/20044/13/2004 12:00:00 AMAPART
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
ELE04-00978 Permanent Service4/12/20044/13/20044/13/2004 12:00:00 AMAPASS
mr lemmon; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
P/S O/H N Ok 4/13/2004 10:25:11 AM
ELE04-01031 Permanent Service4/13/20044/13/20044/13/2004 12:00:00 AMPFAIL
###-#### glenn
cannot have 2 services to a building
conductors for street lights cannot enter the building 4/13/2004 3:36:53 PM
ELE04-01032 Electrical Rough-In4/13/20044/13/20044/13/2004 12:00:00 AMPFAIL
###-#### james
4 violations in one box.
box overfill.
screws inside box.
parallel romex not protected within 1 1/4 in.
romex not supported within 8 in. in several places.
address is west north mountain not north 4/13/2004 1:50:31 PM
ELE04-00375 Electrical Rough-In4/13/20044/13/20044/13/2004 12:00:00 AMPPASS
LLOYD; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ELE04-00375 Final4/13/20044/13/20044/13/2004 12:00:00 AMPPART
LLOYD; Phone #: ###-#### Internet Inspection Request from: Darla Downs
ok except for two sound rooms 4/13/2004 2:12:55 PM