Inspections for the day of: Friday, April 13, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00591 INSP-Sprinkler Rough-in/Hydro4/13/20074/13/20074/13/2007 6:40:18 PMPFAIL
Above ground hydro test failed
FIR07-00158 INSP-Final Inspection4/12/20074/13/20074/13/2007 2:50:02 PMAPASS
permit finaled
FIR06-00964 INSP-Final Inspection4/13/20074/13/20074/13/2007 2:44:17 PMPPASS
permit finaled
FIR06-00723 INSP-Final Inspection4/13/20074/13/20074/13/2007 1:36:08 PMPPASS
permit finaled
FIR06-00536 INSP-Supply line flush4/12/20074/13/20074/13/2007 1:22:25 PMAPASS
Underground flush and hydro test passed.
BLD06-01137 FIRE-Final Inspection4/12/20074/13/20074/13/2007 11:18:50 AMAFAIL
Plan SP-1 whows three fire hydrants installed along Joplin Road. Only two are installed. Provide the third hydrant. The two fire hydrants installed along Joplin Road are mounted too low. See NFPA 24 - 7.3.3. The access gate into the property does not meet the minumum 20' width requirement. Also this gate needs to be provided with an approved entry system such as the Opticon System.
BLD06-01135 FIRE-Final Inspection4/12/20074/13/20074/13/2007 11:16:42 AMAFAIL
Plan SP-1 whows three fire hydrants installed along Joplin Road. Only two are installed. Provide the third hydrant. The two fire hydrants installed along Joplin Road are mounted too low. See NFPA 24 - 7.3.3. The access gate into the property does not meet the minumum 20' width requirement. Also this gate needs to be provided with an approved entry system such as the Opticon System.
BLD06-01142 FIRE-Final Inspection4/12/20074/13/20074/13/2007 11:15:37 AMAFAIL
Plan SP-1 whows three fire hydrants installed along Joplin Road. Only two are installed. Provide the third hydrant. The two fire hydrants installed along Joplin Road are mounted too low. See NFPA 24 - 7.3.3. The access gate into the property does not meet the minumum 20' width requirement. Also this gate needs to be provided with an approved entry system such as the Opticon System.
BLD06-01141 FIRE-Final Inspection4/12/20074/13/20074/13/2007 11:14:10 AMAFAIL
Plan SP-1 whows three fire hydrants installed along Joplin Road. Only two are installed. Provide the third hydrant. The two fire hydrants installed along Joplin Road are mounted too low. See NFPA 24 - 7.3.3. The access gate into the property does not meet the minumum 20' width requirement. Also this gate needs to be provided with an approved entry system such as the Opticon System.
BLD06-01140 FIRE-Final Inspection4/12/20074/13/20074/13/2007 11:12:56 AMAFAIL
Plan SP-1 whows three fire hydrants installed along Joplin Road. Only two are installed. Provide the third hydrant. The two fire hydrants installed along Joplin Road are mounted too low. See NFPA 24 - 7.3.3. The access gate into the property does not meet the minumum 20' width requirement. Also this gate needs to be provided with an approved entry system such as the Opticon System.
BLD06-01139 FIRE-Final Inspection4/12/20074/13/20074/13/2007 11:11:48 AMAFAIL
Plan SP-1 whows three fire hydrants installed along Joplin Road. Only two are installed. Provide the third hydrant. The two fire hydrants installed along Joplin Road are mounted too low. See NFPA 24 - 7.3.3. The access gate into the property does not meet the minumum 20' width requirement. Also this gate needs to be provided with an approved entry system such as the Opticon System.
FIR05-00536 INSP-Sprinkler Rough-in4/12/20074/13/20074/13/2007 9:52:44 AMAPASS
The sprinkler piping above the ceiling in Mission Spec. is ok to cover. Also the piping above the outside main canopy is ok to cover
BLD06-01006 FIRE-Final Inspection4/12/20074/13/20074/13/2007 9:18:09 AMAPASS
life safety passed.