Inspections for the day of: Monday, April 13, 2009.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00234 INSP-Final Inspection4/13/20094/13/20094/17/2009 7:07:33 PMPFAIL
Walkthrough completed for the basement, 1st, 2nd and 3rd floors. Noted plans indicate 18 ah batteries( 7ah are installed) , plans show a nac and one sd in the basement electrical room which are not installed, notification devices at the basement corridor are wall mount type positioned on the ceiling, scope of work per approved plan is not finished for interconnection to the exitsing adjacent builidng alarm devices, noted smoke alarms and audible notification at numerous residential units are incorrectly located per NFPA 72 guidelines, missing lockouts at breakers to the FACP. NOTE: Phone lines, power loss, battery trouble, smoke above panel tested okay. Fire pump and all sprinkler system monitoring points for the basement, 1st and 2nd floors completed okay-need to show accurate locations of basement backflow valves and flow switch and ISO vavles for the standpipe on plans and map. Inspection completed 4/13..
FIR08-00018 INSP-Final Inspection4/10/20094/13/20094/13/2009 5:10:50 PMAPART
Tested interconnections to the fire alarm system for tamper, flow and fire pump monitoring, floor control valves for the basement thru 18th floors tested-need to repair or adjust PRV/flow switches at the 9th and 16th floors.
FIR07-00524 INSP-Final Inspection4/10/20094/13/20094/13/2009 5:07:21 PMPCANC
BLD07-03163 FIRE-Final Inspection4/13/20094/13/20094/13/2009 5:06:48 PMPPASS
Fire life safety inspection passed, correction notice items completed.
BLD08-01454 FIRE-Final Inspection4/10/20094/13/20094/13/2009 12:37:57 PMAFAIL
Delete keyed locking hardware at the beer cooler door, provide approved hardware or remove the exit sign if not required at the stock room freight door.
FIR08-00849 FIR-Aging Inspection4/13/20094/13/20094/13/2009 11:52:44 AM NR
Need site inspection request for work completed and permit final.
FIR07-01051 INSP-Sprinkler Rough-in4/10/20094/13/20094/13/2009 11:50:53 AMAPART
See locations on approved plan set sheet FP5 marked with today's date for ceilings okayed for cover and items in need of correction including two overspaced heads at the kitchen area, missing high temp. head at the storage room near the unit heater, one missing head at the vestibule to the wrestling room, re-pipe supply to one head in the hall, wrestling room ceiling okay for cover, NE classroom wing stairway 2nd floor also okay for cover.
FIR08-00424 INSP-Final Inspection4/10/20094/13/20094/13/2009 11:46:11 AMAPASS
Fire sprinkler permit okayed for final, owner to maintain bags at sprinkler heads within the spray booth per review notes and on site discussion.