Inspections for the day of: Wednesday, April 13, 2011.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00021 FIR-Aging Inspection4/13/20114/13/20114/14/2011 3:16:13 PM NR
I spoke to Mary at Taylor Brothers about the status of the project.
FIR07-00757 FIR-Aging Inspection4/13/20114/13/20114/14/2011 3:07:02 PM NR
I left a voice mail for Ken Webster, Allied General, requesting project status and/or Allied's responcibility.
FIR09-00228 FIR-Aging Inspection4/13/20114/13/20114/14/2011 2:59:13 PM NR
Per Bill the remaining aes inspections are being scheduled
FIR09-00111 FIR-Aging Inspection4/13/20114/13/20114/14/2011 2:58:37 PM NR
Per Bill the remaining aes inspections are being scheduled
BLD11-00475 FIRE-Final Inspection4/13/20114/13/20114/13/2011 3:53:48 PMPPASS
life safety passed.
FIR11-00121 INSP-Sprinkler Rough-in4/12/20114/13/20114/13/2011 2:16:09 PMPPASS
piping is ok to cover. The wrong pendants have been installed per the SIN in the head legend. It appears to be a type error.
FIR11-00120 INSP-Sprinkler Rough-in4/12/20114/13/20114/13/2011 2:14:25 PMPPASS
piping is ok to cover. The wrong pendants have been installed per the SIN in the head legend. It appears to be a type error.
FIR11-00155 INSP-Final Inspection4/12/20114/13/20114/13/2011 2:12:17 PMAPASS
Permit finaled. The suppression system operated correctly.
FIR11-00060 INSP-Final Inspection4/12/20114/13/20114/13/2011 2:08:18 PMPFAIL
provide head wrench, provide signage, provide underground flush, test flow switch
FIR10-00443 INSP-Final Inspection4/13/20114/13/20114/13/2011 11:53:13 AMPPASS
Permit finaled
BLD11-00371 FIRE-Final Inspection4/12/20114/13/20114/13/2011 9:47:11 AMAPASS
life safety passed.
BLD11-00475 FIRE-Final Inspection4/13/20114/13/20114/13/2011 9:46:42 AMAFAIL
Remove the thumbturn dead bolt from the rear exit door.