BLD15-01231
| FIRE-Final Inspection | 4/13/2016 | 4/13/2016 | 4/13/2016 2:00:11 PM | P | PASS |
|
|
Life safety passed
|
BLD15-03428
| FIRE-Final Inspection | 4/12/2016 | 4/13/2016 | 4/13/2016 12:56:22 PM | P | PASS |
|
|
Life safety passed. Previous corrections have been corrected. I tested the emergency off which functioned correctly.
|
BLD16-00832
| FIRE-Final Inspection | 4/13/2016 | 4/13/2016 | 4/13/2016 11:24:02 AM | A | PASS |
|
|
Life safety passed. I spoke with the store manager about maximum storage heights and not to block the corridor with boxes.
|
BLD16-01065
| FIRE-Final Inspection | 4/13/2016 | 4/13/2016 | 4/13/2016 11:12:01 AM | P | PASS |
|
|
life safety passed
|
FIR15-00886
| INSP-Final Inspection | 4/12/2016 | 4/13/2016 | 4/13/2016 9:35:47 AM | A | FAIL |
|
|
Lower the manual pull stations, lower the 15cd ceiling mounted strobe, change candella of the 75 in the work out area to 95, provide notification in the Staff common area. Provide as-builts to Lee of all changes prior to a final inspection.
|
BLD15-03823
| FIRE-Final Inspection | 4/12/2016 | 4/13/2016 | 4/13/2016 9:32:24 AM | A | FAIL |
|
|
Provide sticker at the main exit, provide two additional fire extinguishers as discussed, provide corrected door hardware at the half door and provide final inspection for the fire alarm system.
|
FIR16-00213
| INSP-Sprinkler Rough-in | 4/13/2016 | 4/13/2016 | 4/13/2016 12:00:00 AM | P | CANC |
|
|
Early afternoon please - Spence Phone #: ###-####
|