Inspections for the day of: Wednesday, April 13, 2016.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-01231 FIRE-Final Inspection4/13/20164/13/20164/13/2016 2:00:11 PMPPASS
Life safety passed
BLD15-03428 FIRE-Final Inspection4/12/20164/13/20164/13/2016 12:56:22 PMPPASS
Life safety passed. Previous corrections have been corrected. I tested the emergency off which functioned correctly.
BLD16-00832 FIRE-Final Inspection4/13/20164/13/20164/13/2016 11:24:02 AMAPASS
Life safety passed. I spoke with the store manager about maximum storage heights and not to block the corridor with boxes.
BLD16-01065 FIRE-Final Inspection4/13/20164/13/20164/13/2016 11:12:01 AMPPASS
life safety passed
FIR15-00886 INSP-Final Inspection4/12/20164/13/20164/13/2016 9:35:47 AMAFAIL
Lower the manual pull stations, lower the 15cd ceiling mounted strobe, change candella of the 75 in the work out area to 95, provide notification in the Staff common area. Provide as-builts to Lee of all changes prior to a final inspection.
BLD15-03823 FIRE-Final Inspection4/12/20164/13/20164/13/2016 9:32:24 AMAFAIL
Provide sticker at the main exit, provide two additional fire extinguishers as discussed, provide corrected door hardware at the half door and provide final inspection for the fire alarm system.
FIR16-00213 INSP-Sprinkler Rough-in4/13/20164/13/20164/13/2016 12:00:00 AMPCANC
Early afternoon please - Spence Phone #: ###-####