MEC17-01341
| Rough-in | 4/12/2017 | 4/13/2017 | 4/14/2017 4:32:06 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Petsche
|
MEC17-01343
| Rough-in | 4/12/2017 | 4/13/2017 | 4/13/2017 4:01:22 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Matthew Hansen- need exhast fan in bathroom vented to outdoors
|
MEC17-00659
| Final | 4/13/2017 | 4/13/2017 | 4/13/2017 3:36:13 PM | P | PASS |
|
|
|
MEC17-00150
| Final | 4/13/2017 | 4/13/2017 | 4/13/2017 3:21:38 PM | P | PASS |
|
|
Garage code #1224 Phone #: ###-#### Inspection requested via web by Debbie Marino
|
MEC17-00903
| Rough-in | 4/13/2017 | 4/13/2017 | 4/13/2017 2:51:17 PM | P | PART |
|
|
Need ceiling cover inspection for grid tiles- need 2' t grid and register clips installed on registers- talked to installers there doing now- ok to cover ceiling when this is finished-
|
MEC17-00903
| Final | 4/12/2017 | 4/13/2017 | 4/13/2017 2:26:03 PM | P | CANC |
|
|
Requesting Final inspection for ACAMS job. Dusty is your contact ###-####. Phone #: ###-#### Inspection requested via web by Kathy Youngkin- should have been rough in for cover inspection
|
MEC17-00911
| Final | 4/10/2017 | 4/13/2017 | 4/13/2017 1:43:01 PM | P | PASS |
|
|
please try to call 1 hr before dispatch Phone #: ###-#### Inspection requested via web by Ron Apple
|
MEC16-03224
| Mec-Aging Inspection | 4/13/2017 | 4/13/2017 | 4/13/2017 11:53:00 AM | | PEND |
|
|
talked to Dave contractor- they will try schedule this for final per phone conversation
|
MEC17-01277
| Rough-in | 4/12/2017 | 4/13/2017 | 4/13/2017 11:22:42 AM | A | FAIL |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- combustion air can not be taken from same duct- pan off lower combustion air opening in furnace closets in both units
|
MEC17-01277
| Pressure Test | 4/12/2017 | 4/13/2017 | 4/13/2017 11:21:21 AM | A | PASS |
|
|
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek- unit 101 and 102 20lb gas pass- unit 101 and 102 5lb flue pass
|
MEC17-01319
| Rough-in | 4/12/2017 | 4/13/2017 | 4/13/2017 10:28:47 AM | A | PASS |
|
|
Shaun: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello- R/I ok
|
MEC17-01319
| Pressure Test | 4/12/2017 | 4/13/2017 | 4/13/2017 10:28:15 AM | A | PASS |
|
|
Shaun: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello- 20lb gas pass- 5lb flue pass
|
MEC17-00659
| Final | 4/12/2017 | 4/13/2017 | 4/13/2017 9:58:28 AM | A | NH |
|
|
Phone #: ###-#### Inspection requested via web by Dan Otero- no one home- left notice on front door
|
MEC17-01306
| Final | 4/13/2017 | 4/13/2017 | 4/13/2017 9:44:48 AM | P | PASS |
|
|
|
MEC17-01117
| Final | 4/13/2017 | 4/13/2017 | 4/13/2017 9:12:04 AM | A | PASS |
|
|
|
MEC17-01306
| Rough-in | 4/12/2017 | 4/13/2017 | 4/13/2017 8:57:23 AM | A | PASS |
|
|
CALL HOMEOWNER @ ###-#### TO COORDINATE SCHEDULES 15 MINUTES PRIOR TO ARRIVAL ON SITE Phone #: ###-#### Inspection requested via web by Jason Robinson- R/I ok-
|
MIS17-00113
| MEC-Conference | 4/12/2017 | 4/13/2017 | 4/13/2017 8:17:23 AM | A | DONE |
|
|
possible mechanical work being done without permits- need to pull mech permit for hvac/range hood duct work
|