Inspections for the day of: Thursday, April 13, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01368 ELE-Aging Inspection4/13/20174/13/20174/20/2017 10:50:57 AM PASS
Talk with homeowner and he said everything was inspected and was fine, all notes said they failed.
He will contact the city and try to iron out the issues and correct any problems
MIS17-00113 ELE-Conference4/12/20174/13/20174/13/2017 1:41:47 PMADONE
possible electrical work being done without permits
Work has been done, bathrooms looked like they were redone and wired but covered up also kitchen had been worked on but no walls looked to be opened. Homeowner was not on site, dropped card off to have him call and get a permit.Homeowner will pull a permit for work that has been done
ELE16-03147 Electrical Rough-In4/13/20174/13/20174/13/2017 1:40:15 PMPPASS
Underground. Shane is the contact his cell no is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
underground to pole light/sign ok cover
ELE17-01054 Permanent Service4/12/20174/13/20174/13/2017 1:10:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Randy Fletcher
p/s o/h rec ok
ELE16-01483 Electrical Rough-In4/13/20174/13/20174/13/2017 1:09:38 PMPPASS
We need a soffit inspection for Units 101 ; 107.Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
units 101,107 soffits ok cover
ELE17-00573 Final4/12/20174/13/20174/13/2017 12:10:47 PMPFAIL
owners will be home. Any questions please give me a call. Thank you. Phone #: ###-#### Inspection requested via web by Charmel Kubik
352.30 PVC shall be supported within 36" of a connector
210.8 All 120v receptacles shall have GFCI protection @ tamper resistant type
ELE16-02730 Electrical Rough-In4/12/20174/13/20174/13/2017 10:36:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
All remaining ceilings ok cover
ELE17-00852 Electrical Rough-In4/13/20174/13/20174/13/2017 10:10:44 AMAPASS
Call Rafael for inspection of walls on 2nd floor offices and 1st floor ballroom and women''s restroom area. As close to 0900 as possible, thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo
areas as noted on print walls only ok cover