BLD17-04338
| FIRE-Alarm Testing | 4/12/2018 | 4/13/2018 | 4/13/2018 2:20:31 PM | A | CANC |
|
|
This request is cancelled, inspection request was for fire sprinkler inspection.
|
FIR18-00016
| INSP-Final Inspection | 4/12/2018 | 4/13/2018 | 4/13/2018 2:19:53 PM | P | FAIL |
|
|
Install fire sprinkler head on main sales floor to correct overspace issue. Relocate fire sprinkler in north side of new office area to correct over spacing issue due to column. Install escutcheon on fire sprinkler head in restroom.
|
FIR18-00016
| INSP-Sprinkler Rough-in | 4/13/2018 | 4/13/2018 | 4/13/2018 2:17:05 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in area of work complete, approved for cover.
|
BLD18-00432
| FIRE-Final Inspection | 4/12/2018 | 4/13/2018 | 4/13/2018 10:59:13 AM | A | PASS |
|
|
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher is in place with a current inspection tag, occupancy placard will be place in classroom area before final building inspection. Final life fire safety inspection complete.
|
FIR17-00522
| INSP-Sprinkler Rough-in | 4/10/2018 | 4/13/2018 | 4/13/2018 10:37:16 AM | A | PART |
|
|
Rough to cover inspection for level 1 fire sprinkler piping above sheetrock including dry system for drive through canopy complete, areas where ceiling grid will be installed will need a RTC inspection before covered, overehad fire sprinkler piping located above hardlids on level 1 inluding drive trhough canopy approved for cover.
|
BLD18-00428
| FIRE-Final Inspection | 4/12/2018 | 4/13/2018 | 4/13/2018 9:55:36 AM | A | PASS |
|
|
Life fire safety inspection for area of work complete.
|
FIR18-00108
| INSP-Final Inspection | 4/12/2018 | 4/13/2018 | 4/13/2018 9:55:12 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
|
BLD18-01164
| FIRE-Final Inspection | 4/12/2018 | 4/13/2018 | 4/13/2018 9:11:57 AM | A | PASS |
|
|
No fire sprinklers, no fire alarms, Fire extinguishers are in place with current inspection tags for both suite 100 and 104. Final life fire safety inspection passed/complete.
|
FIR16-00268
| INSP-Final Inspection | 4/13/2018 | 4/13/2018 | 4/13/2018 8:53:23 AM | A | PASS |
|
|
Final fire sprinkler inspection per scope of work complete.
|
BLD18-00308
| FIRE-Final Inspection | 4/12/2018 | 4/13/2018 | 4/13/2018 8:37:40 AM | A | PASS |
|
|
No fire sprinklers, fire alarm inspection is complete, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work complete.
|