Inspections for the day of: Wednesday, April 14, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00024 INSP-Sprinkler Rough-in/Hydro4/13/20044/14/20044/14/2004 12:00:00 AMAPASS
Wet system and dry system hydro test passed 4/14/2004 11:19:38 AM
FIR04-00218 INSP-Sprinkler Rough-in/Hydro4/13/20044/14/20044/14/2004 12:00:00 AMPPASS
thrust blocks ok to cover 4/14/2004 10:05:08 AM
FIR03-00448 INSP-Sprinkler Rough-in4/14/20044/14/20044/14/2004 12:00:00 AMPPASS
second floor corridor sprinkler piping is ok to cover 4/14/2004 4:36:31 PM
BLD04-00097 FIRE-Final Inspection4/14/20044/14/20044/14/2004 12:00:00 AMPPASS
fire life safety finaled 4/14/2004 1:29:31 PM
FIR03-00669 INSP-Sprinkler Rough-in/Hydro4/14/20044/14/20044/14/2004 12:00:00 AMPPART
All items marked for correction on the city approved plans have been corrected except for the upright head in entry lobby 194 is overspaced and the uprights above the gym and cafateria need verified slope match with deck. Ceiling tile is ok to be installed in gym, cafateria and classrooms. 4/14/2004 1:53:45 PM
BLD04-00270 FIRE-Final Inspection4/14/20044/14/20044/14/2004 12:00:00 AMPPASS
fire life safety finaled 4/14/2004 3:16:09 PM
BLD03-00869 FIRE-Final Inspection4/14/20044/14/20044/14/2004 12:00:00 AMPPASS
fire life safety finaled 4/14/2004 3:15:22 PM
FIR04-00024 INSP-Sprinkler Rough-in/Hydro4/14/20044/14/20044/14/2004 12:00:00 AMPPART
Underground hydro test passed 4/14/2004 3:25:31 PM