Inspections for the day of: Tuesday, April 14, 2009.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-00626 Electrical Rough-In4/14/20094/14/20094/14/2009 3:54:32 PMPPASS
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ok
ELE09-00626 Final4/14/20094/14/20094/14/2009 3:54:17 PMPPASS
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten ok
ELE08-02635 Final4/14/20094/14/20094/14/2009 2:56:40 PMPPASS
Alan Phone #: ###-#### ok no card
ELE08-02634 Final4/14/20094/14/20094/14/2009 2:56:15 PMPPASS
Alan Phone #: ###-#### ok no card
ELE08-02633 Final4/14/20094/14/20094/14/2009 2:55:55 PMPPASS
Alan Phone #: ###-#### ok no card
ELE08-01494 Final4/14/20094/14/20094/14/2009 1:56:12 PMPCANC
per Jim Sly see added doc expire for notes
ELE08-01494 DOC - Permit Expired4/14/20094/14/20094/14/2009 1:55:52 PMPPASS
talked with contractor he is no longer doing the work on pool,at this time all work he has done is approved and he wants his permit expired. note a new permit for electrical shall be secured for all future electricalwork required to complete the wiring of pool
ESC09-00098 General Inspection4/14/20094/14/20094/14/2009 12:29:54 PMPPASS
hard surfaces cleaned
ELE08-02635 ELE-Aging Inspection4/14/20094/14/20094/14/2009 11:59:04 AM PART
contr will request final inspection today PM
ELE09-00616 Rough-In Permanent Service4/13/20094/14/20094/14/2009 11:06:27 AMAPASS
alan Phone #: ###-####r/i p/s u/g new ok
ELE09-00615 Rough-In Permanent Service4/14/20094/14/20094/14/2009 10:44:49 AMAPASS
ok for id power to re connect Phone #: ###-#### Internet Inspection Request from: Randy Fletcher r/i p/s u/g rec. ok
ELE08-02740 Permanent Service4/14/20094/14/20094/14/2009 10:00:27 AMAFAIL
Main Panel on North of building ready for power
Phone #: ###-#### Internet Inspection Request from: Don Lustig
corr. met contr, 200.2(B) & 250.24 shall terminate GEC to grounded bus and install main bonding jumper or screw, 110.3(A) replace damaged wire at p/s (ringed the wire)300.4(G) & 352.46 provide connectors, of bushings where u/g enters bottom of service job not ready also
ESC08-00539 General Inspection4/14/20094/14/20094/14/2009 9:55:26 AMAPASS
ok
ELE09-00061 ELE-Aging Inspection4/14/20094/14/20094/14/2009 9:03:22 AM PART
called wsuc contr will call when ready
ESC09-00098 General Inspection4/13/20094/14/20094/14/2009 8:57:09 AMAPART
Ray ###-####stopped at site some cleanup done, cleanup in progress will check back in the PM
ELE09-00615 Rough-In Permanent Service4/14/20094/14/20094/14/2009 7:26:45 AMPCANC
Ok for Id power to re-connect. Randy ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher Inspection cancelled from web by: Randy Fletcher