FIR08-00234
| INSP-Final Inspection | 4/13/2009 | 4/14/2009 | 4/17/2009 7:07:55 PM | P | PART |
|
|
On site meeting regarding heights at audible notification devices in the residential units, listing for wall mounted appliances that appear to be ceiling type, item #6 regarding sprinkler system monitoring interface for the existing building per temporary occupancy agreement letter, field modifications, project phasing for completion of work indicated per approved fire alarm plans, and locations for smoke alarms to be in compliance with NFPA 72 chaper 11. Completed testing for fire sprinkler floor control manifolds at floors 5 thru 18, noted 9th and 16th floor flow switches failed to operate, need to relocate control valves. Inspection completed 4/14..
|
FIR08-00018
| INSP-Final Inspection | 4/14/2009 | 4/14/2009 | 4/14/2009 5:37:39 PM | P | DEFR |
|
|
See inspection comments per T. Frost.
|
FIR08-00856
| FIR-Aging Inspection | 4/14/2009 | 4/14/2009 | 4/14/2009 5:36:48 PM | | NR |
|
|
Need request for site inspection.
|
BLD06-02303
| FIRE-Final Inspection | 4/13/2009 | 4/14/2009 | 4/14/2009 5:35:22 PM | P | NR |
|
|
Project related fire alarm and sprinkler permits must be approved prior to final inspection for building fire life safety.
|
BLD08-01454
| FIRE-Final Inspection | 4/13/2009 | 4/14/2009 | 4/14/2009 5:31:42 PM | A | PASS |
|
|
Noted correction items repaired, fire life safety finaled.
|
FIR08-00667
| INSP-Alarm Testing | 4/13/2009 | 4/14/2009 | 4/14/2009 5:30:49 PM | A | PART |
|
|
Fire alarm interconnections for the east half (right hand side) of the new tool passed inspection.
|
BLD09-00002
| FIRE-Final Inspection | 4/13/2009 | 4/14/2009 | 4/14/2009 5:28:58 PM | A | FAIL |
|
|
The new pair of partition doors when closed create a non-sprinklered space, need to provide missing suite address numbers, provide approved door hardware at the west exits, post max. occupant load signs per review comments, provide directional arrow at the second exit sign for the bar area.
|