Inspections for the day of: Tuesday, April 14, 2009.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00234 INSP-Final Inspection4/13/20094/14/20094/17/2009 7:07:55 PMPPART
On site meeting regarding heights at audible notification devices in the residential units, listing for wall mounted appliances that appear to be ceiling type, item #6 regarding sprinkler system monitoring interface for the existing building per temporary occupancy agreement letter, field modifications, project phasing for completion of work indicated per approved fire alarm plans, and locations for smoke alarms to be in compliance with NFPA 72 chaper 11. Completed testing for fire sprinkler floor control manifolds at floors 5 thru 18, noted 9th and 16th floor flow switches failed to operate, need to relocate control valves. Inspection completed 4/14..
FIR08-00018 INSP-Final Inspection4/14/20094/14/20094/14/2009 5:37:39 PMPDEFR
See inspection comments per T. Frost.
FIR08-00856 FIR-Aging Inspection4/14/20094/14/20094/14/2009 5:36:48 PM NR
Need request for site inspection.
BLD06-02303 FIRE-Final Inspection4/13/20094/14/20094/14/2009 5:35:22 PMPNR
Project related fire alarm and sprinkler permits must be approved prior to final inspection for building fire life safety.
BLD08-01454 FIRE-Final Inspection4/13/20094/14/20094/14/2009 5:31:42 PMAPASS
Noted correction items repaired, fire life safety finaled.
FIR08-00667 INSP-Alarm Testing4/13/20094/14/20094/14/2009 5:30:49 PMAPART
Fire alarm interconnections for the east half (right hand side) of the new tool passed inspection.
BLD09-00002 FIRE-Final Inspection4/13/20094/14/20094/14/2009 5:28:58 PMAFAIL
The new pair of partition doors when closed create a non-sprinklered space, need to provide missing suite address numbers, provide approved door hardware at the west exits, post max. occupant load signs per review comments, provide directional arrow at the second exit sign for the bar area.