BLD11-00736
| FIRE-Final Inspection | 4/14/2011 | 4/14/2011 | 4/14/2011 3:05:48 PM | P | FAIL |
|
|
Provide approved hardware for both exterior exit doors and the new interior doors as discussed and provide a fire extinguisher with a current inspection tag mounted in a normal path of travel.
|
FIR10-00297
| FIR-Aging Inspection | 4/14/2011 | 4/14/2011 | 4/14/2011 2:47:17 PM | | NR |
|
|
Per Bill the remaining aes inspections are being scheduled
|
FIR11-00158
| INSP-Sprinkler Rough-in | 4/14/2011 | 4/14/2011 | 4/14/2011 2:46:00 PM | P | PASS |
|
|
Sprinkler piping is ok to cover.
|
BLD11-00364
| FIRE-Conference | 4/14/2011 | 4/14/2011 | 4/14/2011 2:11:26 PM | P | DONE |
|
|
Daniel and I wnet over life safety requirements. Per Carl the security gate near the main lobby can remain if the exit sign over the main exit is relocated to the door behind the reception desk. With this relocated exit sign and the other one leading to the second door, two exits from the waiting area are provided.
|
FIR11-00060
| INSP-Supply line flush | 4/14/2011 | 4/14/2011 | 4/14/2011 12:50:55 PM | P | PASS |
|
|
Supply line flush and the testing of the flow switch passed.
|