Inspections for the day of: Friday, April 14, 2017.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorScott Arellano
TitleFIRE PLAN REVIEWER
Phone #208-608-7109
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF17-00026 INSP-Final4/14/20174/14/20174/14/2017 3:10:57 PMPPASS
Alarm inspection finaled
NAF15-00041 INSP-Supply line flush4/13/20174/14/20174/14/2017 3:04:29 PMPPASS
Flush Completed
NAF16-00012 INSP-Final4/13/20174/14/20174/14/2017 3:02:20 PMPFAIL
Hallway Sprinkler heads obstructed by ceiling light fixture at multiple units. Sprinkler heads need to be relocated to 36 inches from fixture or fixtures need to be replaced with recessed lighting.
NAF15-00026 INSP-Final4/13/20174/14/20174/14/2017 2:49:48 PMPFAIL
1) Unit smoke alarms need to be relocated a minimum 36 inches from bathroom doors.
2) Residential Emergency Guides must be produced and located in each dwelling unit.
NAF17-00025 INSP-Conference4/13/20174/14/20174/14/2017 11:48:46 AMPDONE
Conference completed in AM.
NAF17-00026 INSP-Sprinkler Rough-in/Hydro4/13/20174/14/20174/14/2017 8:51:42 AMPCANC
Call prior to going Phone #: 8712473 >> Inspection requested via mobile web by Jack Schmidt