NAF17-00026
| INSP-Final | 4/14/2017 | 4/14/2017 | 4/14/2017 3:10:57 PM | P | PASS |
|
|
Alarm inspection finaled
|
NAF15-00041
| INSP-Supply line flush | 4/13/2017 | 4/14/2017 | 4/14/2017 3:04:29 PM | P | PASS |
|
|
Flush Completed
|
NAF16-00012
| INSP-Final | 4/13/2017 | 4/14/2017 | 4/14/2017 3:02:20 PM | P | FAIL |
|
|
Hallway Sprinkler heads obstructed by ceiling light fixture at multiple units. Sprinkler heads need to be relocated to 36 inches from fixture or fixtures need to be replaced with recessed lighting.
|
NAF15-00026
| INSP-Final | 4/13/2017 | 4/14/2017 | 4/14/2017 2:49:48 PM | P | FAIL |
|
|
1) Unit smoke alarms need to be relocated a minimum 36 inches from bathroom doors.
2) Residential Emergency Guides must be produced and located in each dwelling unit.
|
NAF17-00025
| INSP-Conference | 4/13/2017 | 4/14/2017 | 4/14/2017 11:48:46 AM | P | DONE |
|
|
Conference completed in AM.
|
NAF17-00026
| INSP-Sprinkler Rough-in/Hydro | 4/13/2017 | 4/14/2017 | 4/14/2017 8:51:42 AM | P | CANC |
|
|
Call prior to going Phone #: 8712473 >> Inspection requested via mobile web by Jack Schmidt
|