Inspections for the day of: Tuesday, April 14, 2020.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04502 Electrical Rough-In4/14/20204/14/20204/14/2020 1:45:41 PMPPASS
PT deck L2 pour2 Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Pour covers south side of level 2 and ramp to level 3, rough in ok cover
ELE19-04799 Electrical Rough-In4/13/20204/14/20204/14/2020 1:09:37 PMPPASS
Elevated deck rough in
4th floor northwest corner Phone #: ###-#### Inspection requested via web by Jason Parke
Pour noted rough in ok cover.
ELE20-00179 Electrical Rough-In4/14/20204/14/20204/14/2020 11:33:33 AMPPASS
John ###-####
Basement rough in ok cover.
ELE20-00179 Conference4/14/20204/14/20204/14/2020 11:13:26 AMPPASS
Discussed what areas of band shell stage area are damp locations and wet locations.
As per 406.9 (A) and (B) for 15 and 20 amp, 125 to 250 volt receptacles, the first 12' from the front of overhang shall be considered a wet location subject to beating rain, remaining area beyond 12' back from the front of overhang shall be considered a damp location.
406.9 (B)(2)(b) shall apply to other ampacities due to a band member would not leave their equipment unattended.
Determinations made with Daryl Degrange Chief Electrical Inspector and John with AME Electric on site.