BLD19-04017
| FIRE-Final Inspection | 4/13/2020 | 4/14/2020 | 4/14/2020 3:33:34 PM | P | FAIL |
|
|
Ansul systems that was protecting the de-commissioned paint booth will need to be removed, a demo FIR permit is required for removal of the fire system. Provide single action door hardware on main entry as discussed, door hardware in place would not operate when locked. Provide fire extinguishers with current inspection tags and place as discussed. Provide maximum occupancy placard as shown on city approved drawings. Provide code compliant addressing on the fire access side of the building as discussed.
*screened* Check Ansul system, please call ahead for access - Paul Phone #: ###-####
|
FIR19-00785
| INSP-Sprinkler Rough-in | 4/14/2020 | 4/14/2020 | 4/14/2020 3:28:57 PM | P | CANC |
|
|
Inspection request had to cancelled due to inspection load/manpower shortage. Per conversation with point of contact, inspection request will be rescheduled by the contractor, this request is cancelled.
Screened- Tanner Phone #: ###-####
|
BLD19-02706
| FIRE-Final Inspection | 4/13/2020 | 4/14/2020 | 4/14/2020 3:20:09 PM | P | CANC |
|
|
Cancelled per conversation with point of contact, will be rescheduled after FIR permit for fire alarm system is complete.
Screened call to meet // Bill Phone #: ###-####
|
FIR19-00836
| INSP-Sprinkler Rough-in | 4/10/2020 | 4/14/2020 | 4/14/2020 1:48:07 PM | P | PART |
|
|
Notated city approved drawings with red ink for preset hangers to be covered.
THIS IS FOR THE MECH. ROOM ON 1ST FLOOR. JUSTIN NELSON IS OUR ON SITE FOREMAN. Phone #: ###-#### Inspection requested via web by Brad Bettencourt
|
BLD18-00842
| FIRE-Final Inspection | 4/14/2020 | 4/14/2020 | 4/14/2020 1:09:33 PM | P | FAIL |
|
|
Emergency lights on the northeast side of the building did not function when AC power was isolated.
Screened- Steve Phone #: ###-####
|
FIR20-00258
| INSP-Final Inspection | 4/14/2020 | 4/14/2020 | 4/14/2020 11:54:45 AM | A | PASS |
|
|
Final fire sprinkler inspection for scope of work is complete.
|
FIR20-00258
| INSP-Sprinkler Rough-in | 4/14/2020 | 4/14/2020 | 4/14/2020 11:54:17 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping in scope of work is complete, approved for cover.
Screened- Rick Phone #: ###-####
|
FIR20-00138
| INSP-Sprinkler Rough-in | 4/14/2020 | 4/14/2020 | 4/14/2020 10:53:03 AM | P | PASS |
|
|
Texted photos have been received for scope of work, per photos scope of work is approved for cover.
Please see texted photos Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD19-03480
| FIRE-Final Inspection | 4/9/2020 | 4/14/2020 | 4/14/2020 10:48:09 AM | A | FAIL |
|
|
FIR permit (FIR20-00140) for hood suppression system needs to be finaled before life fire safety can be completed.
Inspector please call 30 minutes before arrival Phone #: ###-#### Inspection requested via web by kevin debelloy
|
FIR20-00140
| INSP-Final Inspection | 4/13/2020 | 4/14/2020 | 4/14/2020 10:46:26 AM | A | CANC |
|
|
Make-up air for hood not operational according to point of contact, this request is cancelled per conversation with point of contact.
Phone #: 2084777315 >> Inspection requested via mobile web by Matt Robison
|
FIR20-00045
| INSP-Sprinkler Rough-in | 4/13/2020 | 4/14/2020 | 4/14/2020 10:03:13 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping above hardlids in area of work is complete, city approved plans have been notated with red ink areas approved for cover.
Rough in for hard lids. Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR20-00057
| INSP-Sprinkler Rough-in | 4/13/2020 | 4/14/2020 | 4/14/2020 10:01:49 AM | A | PART |
|
|
Partial rough to cover inspection for overhead fire sprinkler piping above hardlids in area of work is complete, city approved plans have been notated with red ink areas approved for cover.
Phone #: ###-#### Inspection requested via web by Sam Ball
|
FIR19-00661
| INSP-Final Inspection | 4/9/2020 | 4/14/2020 | 4/14/2020 9:40:43 AM | A | FAIL |
|
|
Fire sprinkler system is required to be supervised per the 2015 IFC, section 903.4.
Josh Danes Cell Number: ###-#### Phone #: ###-#### Inspection requested via web by Connie Danes
|
FIR20-00125
| INSP-Sprinkler Rough-in | 4/13/2020 | 4/14/2020 | 4/14/2020 9:36:01 AM | A | PASS |
|
|
All tenting in place at time of inspection, cover is approved. Sticker has been placed for cover approval.
tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00119
| INSP-Sprinkler Rough-in | 4/13/2020 | 4/14/2020 | 4/14/2020 9:23:42 AM | A | FAIL |
|
|
piping completely wrapped with insulation, pocket between sheetrock and piping not provided, cover is not approved.
tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|
FIR20-00120
| INSP-Sprinkler Rough-in | 4/13/2020 | 4/14/2020 | 4/14/2020 9:22:13 AM | A | FAIL |
|
|
Piping is completely wrapped in 4 areas, pocket is not provided for freeze protection. One area is not covered correctly, pocket between sheetrock and piping will be comprimised, cover is not approved.
cover is wrapped tenting Phone #: ###-#### Inspection requested via web by Jonathan Lee
|