FIR01-00562
| INSP-Sprinkler Rough-in | 4/15/2002 | 4/15/2002 | 4/15/2002 12:00:00 AM | P | PART |
|
|
r/i sam ###-#### the 6 inch lines for future concourse are okay to cover; will need one more section to complete. will require flush and hydro 4/15/2002 3:03:40 PM
|
BLD00-02242
| FIRE-Conference | 4/15/2002 | 4/15/2002 | 4/15/2002 12:00:00 AM | P | PART |
|
|
harold ###-#### for conf met with Harold of Mountain Power; since an elevator is now in the building, an elevator recall control unit will be required per NFPA 72 para 3-9.3.1; he was going to get Dave Maxwell to submit plans 4/15/2002 3:27:10 PM
|
BLD02-00272
| FIRE-Final Inspection | 4/15/2002 | 4/15/2002 | 4/15/2002 12:00:00 AM | P | FAIL |
|
|
TEMPORARY IN 1 ROOM ###-#### ALAN exit sign not working at south exit; occupant load sign; fire extinguishers hung; told Alan that Dave Miller has to approve temp occupancy 4/15/2002 3:58:30 PM
|