Inspections for the day of: Monday, April 15, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00349 FIRE-Final Inspection4/12/20024/15/20024/15/2002 12:00:00 AMAFAIL
provide permits if needed for review note #1, provide annual inspection tag for fire extinguishers, provide sticker on main exit, mount and test exit/emergency lights at both basement exits, verify cfm rating of the HVAC system, install door and seal penatrations in basement 4/15/2002 10:57:17 AM
FIR02-00038 INSP-Conference4/15/20024/15/20024/15/2002 12:00:00 AMADONE
I spoke with Phil (###-####) and notified him that the existing elevator recall system will need to be intergrated with the new fire alarm system per NFPA 72 and that plans will need to be submitted for approval. The fire alarm panel as tested is operational
FIR02-00026 INSP-Final Inspection4/12/20024/15/20024/15/2002 12:00:00 AMPFAIL
need to test one last fire/smoke damper and all duct detectors and verify signals 4/15/2002 5:16:35 PM
FIR02-00099 INSP-Sprinkler Rough-in/Hydro4/15/20024/15/20024/15/2002 12:00:00 AMPPASS
hydro test ok. rough-in for outside canopy and barrel area ok for cover 4/15/2002 3:37:19 PM