FIR03-00343
| INSP-Sprinkler Rough-in/Hydro | 4/14/2004 | 4/15/2004 | 4/15/2004 12:00:00 AM | A | PART |
|
|
Contact - Terry -- Hyrdo on Dry System ; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley hydro test for dry systems and dry standpipe okay; need through-bolts on EQ in cinder block; heads obstructed by conduit, etc; air compressor has on/off switch; pressure sensing lines shall be copper/brass - see NFPA 20 and plans; need flow switch on supervised main (from BFP to pump) 4/15/2004 11:32:23 AM
|
FIR04-00010
| INSP-Final Inspection | 4/14/2004 | 4/15/2004 | 4/15/2004 12:00:00 AM | A | FAIL |
|
|
please call teri before going out ; Phone #: ###-#### Internet Inspection Request from: Darla Downs Resubmittals needed for 6 new tampers on the anti-freeze loop and deletion of the knox box tamper; sign on riser door; address was wrong the monitoring account 4/15/2004 1:52:39 PM
|
FIR03-00250
| INSP-Alarm Testing | 4/14/2004 | 4/15/2004 | 4/15/2004 12:00:00 AM | A | PASS |
|
|
Let me know what time would work for you so that I can schedule it with the building
management.; Phone #: ###-#### Internet Inspection Request from: Rick Groom
|
FIR03-00477
| INSP-Final Inspection | 4/12/2004 | 4/15/2004 | 4/15/2004 12:00:00 AM | P | FAIL |
|
|
Contact: Mike -- will be ready after 1pm; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Outside bell not working - couldn't locate breaker which will need lockout; tampers on BFP need to be locked open; need sign on FDC indicating basement only sprinkler system 4/15/2004 3:16:48 PM
|
FIR03-00816
| INSP-Sprinkler Rough-in/Hydro | 4/15/2004 | 4/15/2004 | 4/15/2004 12:00:00 AM | P | FAIL |
|
|
pager #///jeff; Phone #: ###-#### Internet Inspection Request from: Barbara Moore racking system dropped 5 psi; overhead and canopy system hydro okay 4/15/2004 12:47:33 PM
|
FIR03-00725
| INSP-Sprinkler Rough-in/Hydro | 4/15/2004 | 4/15/2004 | 4/15/2004 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 4/15/2004 at 9:51:31 AM. Contact: ###-####. North side rooms okay to cover; heads in corridor and east room heads not cut to ceiling 4/15/2004 2:45:35 PM
|
FIR04-00083
| INSP-Sprinkler Rough-in | 4/14/2004 | 4/15/2004 | 4/14/2004 12:00:00 AM | A | PASS |
|
|
sam; Phone #: ###-#### Internet Inspection Request from: Barbara Moore UG okay to cover - completed to street; still need flush and hydro 4/14/2004 3:58:23 PM
|
FIR03-00477
| INSP-Final Inspection | 4/12/2004 | 4/15/2004 | 4/12/2004 3:00:05 PM | A | CANC |
|
|
Contact _ Mike; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|