FIR05-00016
| INSP-Supply line flush | 4/14/2005 | 4/15/2005 | 4/15/2005 2:40:28 PM | P | PASS |
|
|
Fire supply line flush satisfactory.
|
FIR05-00093
| INSP-Sprinkler Rough-in/Hydro | 4/15/2005 | 4/15/2005 | 4/15/2005 12:48:36 PM | P | CANC |
|
|
###-#### Jim Cancel inspection per. Jim Danes, not ready - will re-schedule next week.
|
BLD05-00282
| FIRE-Final Inspection | 4/15/2005 | 4/15/2005 | 4/15/2005 11:45:47 AM | P | PART |
|
|
Fire life safety, Temp. occupancy given per. Dave Lokker.
|
FIR05-00154
| INSP-Final Inspection | 4/14/2005 | 4/15/2005 | 4/15/2005 11:08:05 AM | A | FAIL |
|
|
Re-submitted approved plans and notes not available for review. Job supervisor seeks temp. occupancy approval.
|
FIR05-00117
| INSP-Sprinkler Rough-in | 4/14/2005 | 4/15/2005 | 4/15/2005 9:22:34 AM | A | FAIL |
|
|
Sprinkler upright opposite entry 101 wall is not installed as shown on plan causing adjacent head to be overspaced. Two added uprights on sheet FP2 south side line do not meet minimum separation requirements.
|
BLD05-00282
| FIRE-Sprinkler Rough-in | 4/15/2005 | 4/15/2005 | 4/15/2005 12:00:00 AM | P | PASS |
|
|
Fire sprinkler finaled.
|
BLD05-00282
| FIRE-Alarm Testing | 4/15/2005 | 4/15/2005 | 4/15/2005 12:00:00 AM | P | PART |
|
|
Fire alarm, Temp. occupancy given per. Dave Lokker.
|
FIR05-00016
| INSP-Sprinkler Rough-in/Hydro | 4/15/2005 | 4/15/2005 | 4/15/2005 12:00:00 AM | P | PASS |
|
|
Underground fire supply line hydrostatic test passed.
|