Inspections for the day of: Tuesday, April 15, 2008.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00969 INSP-Sprinkler Rough-in4/15/20084/15/20084/16/2008 4:51:50 PMPPASS
The remaining underground is ok to cover
BLD08-00554 FIRE-Final Inspection4/15/20084/15/20084/15/2008 4:38:00 PMPFAIL
Provide signage as discussed for the maximum storage height of 17'. Provide the required 6" flu space. Provide column protection or relocate the racks as discussed. Finish installing the remaining racks.
BLD08-00170 FIRE-Final Inspection4/14/20084/15/20084/15/2008 4:36:20 PMAFAIL
provide fire alarm permit for the interconnection between the new door magnet and the existing fire alarm system
BLD08-00727 FIRE-Final Inspection4/14/20084/15/20084/15/2008 12:58:16 PMAPASS
life safety passed
BLD08-00305 FIRE-Final Inspection4/14/20084/15/20084/15/2008 6:48:20 AMAPASS
life safety passed
FIR08-00189 INSP-Final Inspection4/11/20084/15/20084/15/2008 6:47:35 AMAPASS
permit finaled
FIR08-00200 INSP-Final Inspection4/14/20084/15/20084/14/2008 11:13:05 AMACANC
Final Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley