Inspections for the day of: Friday, April 15, 2011.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-00550 FIRE-Final Inspection4/15/20114/15/20114/18/2011 4:27:00 PMAPART
Reinspection scheduled 4/19 AM.
FIR11-00129 INSP-Final Inspection4/15/20114/15/20114/18/2011 4:03:33 PMPPASS
Fire sprinkler permit work approved for final status.
FIR11-00097 INSP-Final Inspection4/15/20114/15/20114/18/2011 4:02:32 PMPPASS
Scope of work completed. Fire sprinkler permit finaled.
BLD10-02172 FIRE-Final Inspection4/15/20114/15/20114/15/2011 4:40:14 PMPPART
Verified offsite monitoring for the fire sprinkler system. Final pending stem at the wall post indicator valve to the NRS at the riser.
BLD10-00974 FIRE-Final Inspection4/15/20114/15/20114/15/2011 4:39:46 PMPPART
Verified offsite monitoring for the fire sprinkler system. Final pending stem at the wall post indicator valve to the NRS at the riser.
FIR11-00112 INSP-Final Inspection4/14/20114/15/20114/15/2011 4:36:17 PMAPASS
Scope of fire sprinkler work passed final inspection. Noted existing system is overdue annual inspection and will need to be made current prior to building permit fire life safety final.
FIR11-00101 INSP-Final Inspection4/14/20114/15/20114/15/2011 4:34:03 PMAFAIL
Noted overspaced coverage at the design room adjacent to the new sheetrock partition wall at the roof deck to patio access storefront.
BLD11-00554 FIRE-Final Inspection4/15/20114/15/20114/15/2011 4:29:53 PMANR
Pending correction items.
FIR08-00802 INSP-Final Inspection4/14/20114/15/20114/15/2011 4:29:19 PMAPASS
Sprinkler monitoring only including offsite reporting verified for functionality.