Inspections for the day of: Wednesday, April 15, 2015.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00774 ELE-Aging Inspection4/15/20154/15/20154/21/2015 3:12:09 PM DONE
Drove by and inspected
ELE13-00756 ELE-Aging Inspection4/15/20154/15/20154/21/2015 7:03:37 AM CANC
too busy
ELE14-03526 Final4/15/20154/15/20154/16/2015 12:54:13 PMPFAIL
This permit was to cover main service outside and sub-feed to sub panel only. No branch circuits or interior wiring included. Interior wiring cover by permit ELE14-02852. NEC 240.24(E)- Overcurrent devices shall not be located in a bathroom.
BCC 4-05-31- Panel location shall not be installed in a bathroom.
ELE15-01033 Temporary Service4/15/20154/15/20154/16/2015 8:07:05 AMPPASS
Overhead temp pole in back of lot Phone #: ###-#### Inspection requested via web by Heath Thomas t/s o/h n ok
ELE15-00940 Electrical Rough-In4/15/20154/15/20154/16/2015 6:51:58 AMPNR
As late as possible >> Inspection requested via mobile web by Mike Turned into conference. Need to add outlet for counter top right of sink, larger junction box for range junction, shall have range box for new range location
ELE13-03105 Final4/15/20154/15/20154/15/2015 2:58:33 PMPPART
Final the thk bldg Phone #: ###-#### Inspection requested via web by matt miller Some valuation on this permit covers work in other areas. New permit to be pulled for other work. Temp final ok
ELE15-01034 Rough-In Permanent Service4/15/20154/15/20154/15/2015 1:49:17 PMPPASS
rough-in Phone #: ###-#### Inspection requested via web by cal crosby Rough in ok cover p/s u/g n ok
ELE13-00683 Final4/14/20154/15/20154/15/2015 1:18:05 PMPPASS
Phone #: ###-#### Inspection requested via web by Tim Dunlop Final ok
ELE14-03470 Final4/15/20154/15/20154/15/2015 12:55:04 PMPPASS
Install 1 pole sign. All primary power by others. Permit ELE15-00821 was pulled to run circuit by Enterprise Electric Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
ELE14-02852 Final4/14/20154/15/20154/15/2015 11:49:34 AMAFAIL
Charles// please call before Phone #: ###-#### 210.8- All receptacle outlet 15 or 20 amp 120 volt shall have GFCI protection.
406.12- All 15 or 20 amp 120 volt receptacle outlets shall be tamper resistant type. Only few were rewired.
240.24(E)- Over current devices shall not be located in a bathroom.
4-05-31- Panel location shall not be installed in a bathroom.
ELE15-01025 Final4/14/20154/15/20154/15/2015 10:59:10 AMAPASS
Suite #120 Business Name: Positive Action. Phone #: ###-#### Inspection requested via web by Randy Fletcher Circuit added for copier Final ok
ELE15-01032 Rough-In Permanent Service4/15/20154/15/20154/15/2015 10:23:02 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Contractor to make ground rod flush with grade. Rough in ok cover p/s u/g n ok
ELE15-00928 Rough-In Permanent Service4/15/20154/15/20154/15/2015 9:53:29 AMAPASS
Cody is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
ELE14-02449 Final4/14/20154/15/20154/15/2015 9:17:14 AMAPASS
lock box #5050 Phone #: ###-#### Inspection requested via web by Eric Schroeder Final ok
ELE14-02449 Permanent Service4/15/20154/15/20154/15/2015 9:16:37 AMPPASS
lock box #5050 Phone #: ###-#### Inspection requested via web by Eric Schroeder Service reconnect ok p/s u/g rec ok
ELE15-01001 Temporary Service4/15/20154/15/20154/15/2015 8:17:51 AMAPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov t/s u/g n ok