ELE13-00774
| ELE-Aging Inspection | 4/15/2015 | 4/15/2015 | 4/21/2015 3:12:09 PM | | DONE |
|
|
Drove by and inspected
|
ELE13-00756
| ELE-Aging Inspection | 4/15/2015 | 4/15/2015 | 4/21/2015 7:03:37 AM | | CANC |
|
|
too busy
|
ELE14-03526
| Final | 4/15/2015 | 4/15/2015 | 4/16/2015 12:54:13 PM | P | FAIL |
|
|
This permit was to cover main service outside and sub-feed to sub panel only. No branch circuits or interior wiring included. Interior wiring cover by permit ELE14-02852. NEC 240.24(E)- Overcurrent devices shall not be located in a bathroom. BCC 4-05-31- Panel location shall not be installed in a bathroom.
|
ELE15-01033
| Temporary Service | 4/15/2015 | 4/15/2015 | 4/16/2015 8:07:05 AM | P | PASS |
|
|
Overhead temp pole in back of lot Phone #: ###-#### Inspection requested via web by Heath Thomas t/s o/h n ok
|
ELE15-00940
| Electrical Rough-In | 4/15/2015 | 4/15/2015 | 4/16/2015 6:51:58 AM | P | NR |
|
|
As late as possible >> Inspection requested via mobile web by Mike Turned into conference. Need to add outlet for counter top right of sink, larger junction box for range junction, shall have range box for new range location
|
ELE13-03105
| Final | 4/15/2015 | 4/15/2015 | 4/15/2015 2:58:33 PM | P | PART |
|
|
Final the thk bldg Phone #: ###-#### Inspection requested via web by matt miller Some valuation on this permit covers work in other areas. New permit to be pulled for other work. Temp final ok
|
ELE15-01034
| Rough-In Permanent Service | 4/15/2015 | 4/15/2015 | 4/15/2015 1:49:17 PM | P | PASS |
|
|
rough-in Phone #: ###-#### Inspection requested via web by cal crosby Rough in ok cover p/s u/g n ok
|
ELE13-00683
| Final | 4/14/2015 | 4/15/2015 | 4/15/2015 1:18:05 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tim Dunlop Final ok
|
ELE14-03470
| Final | 4/15/2015 | 4/15/2015 | 4/15/2015 12:55:04 PM | P | PASS |
|
|
Install 1 pole sign. All primary power by others. Permit ELE15-00821 was pulled to run circuit by Enterprise Electric Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
|
ELE14-02852
| Final | 4/14/2015 | 4/15/2015 | 4/15/2015 11:49:34 AM | A | FAIL |
|
|
Charles// please call before Phone #: ###-#### 210.8- All receptacle outlet 15 or 20 amp 120 volt shall have GFCI protection. 406.12- All 15 or 20 amp 120 volt receptacle outlets shall be tamper resistant type. Only few were rewired. 240.24(E)- Over current devices shall not be located in a bathroom. 4-05-31- Panel location shall not be installed in a bathroom.
|
ELE15-01025
| Final | 4/14/2015 | 4/15/2015 | 4/15/2015 10:59:10 AM | A | PASS |
|
|
Suite #120 Business Name: Positive Action. Phone #: ###-#### Inspection requested via web by Randy Fletcher Circuit added for copier Final ok
|
ELE15-01032
| Rough-In Permanent Service | 4/15/2015 | 4/15/2015 | 4/15/2015 10:23:02 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Contractor to make ground rod flush with grade. Rough in ok cover p/s u/g n ok
|
ELE15-00928
| Rough-In Permanent Service | 4/15/2015 | 4/15/2015 | 4/15/2015 9:53:29 AM | A | PASS |
|
|
Cody is the onsite contact at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
|
ELE14-02449
| Final | 4/14/2015 | 4/15/2015 | 4/15/2015 9:17:14 AM | A | PASS |
|
|
lock box #5050 Phone #: ###-#### Inspection requested via web by Eric Schroeder Final ok
|
ELE14-02449
| Permanent Service | 4/15/2015 | 4/15/2015 | 4/15/2015 9:16:37 AM | P | PASS |
|
|
lock box #5050 Phone #: ###-#### Inspection requested via web by Eric Schroeder Service reconnect ok p/s u/g rec ok
|
ELE15-01001
| Temporary Service | 4/15/2015 | 4/15/2015 | 4/15/2015 8:17:51 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov t/s u/g n ok
|