FIR14-00708
| INSP-Sprinkler Rough-in | 4/15/2015 | 4/15/2015 | 4/15/2015 4:49:15 PM | P | FAIL |
|
|
Bldg G wet system 2nd Floor , no approval for cover at this time due to significant field modifications, requiring plan resubmittial. Modifications include changes to remote area.
|
FIR14-00531
| INSP-Sprinkler Rough-in | 4/14/2015 | 4/15/2015 | 4/15/2015 4:10:59 PM | A | PART |
|
|
Floors 4, 3 and podium in tower 4 living quarters ok to cover, except room 204 with overspaced bedroom head and room 200 missing closet head. Soffits in tower 3 ok to cover.
|
FIR13-00167
| INSP-Sprinkler Rough-in | 4/15/2015 | 4/15/2015 | 4/15/2015 4:07:56 PM | P | CANC |
|
|
Cancelled to be rescheduled per phone conversation with contractor.
|
FIR14-00815
| INSP-Sprinkler Rough-in | 4/13/2015 | 4/15/2015 | 4/15/2015 3:12:02 PM | P | DEFR |
|
|
Rescheduled for 4/16 per discussion with contractor
|
BLD15-00071
| FIRE-Final Inspection | 4/15/2015 | 4/15/2015 | 4/15/2015 3:09:25 PM | P | FAIL |
|
|
Contractor to replace door hardware according to plan, exiting discharge light at service entrance, contractor not prepared to test duct smoke detectors and building number needs to be contrasting.
|
FIR15-00112
| INSP-Sprinkler Rough-in/Hydro | 4/14/2015 | 4/15/2015 | 4/15/2015 3:07:00 PM | A | PART |
|
|
Second Flr Hydrostatic testing of new system piping complete ok. Heads at new ceilings and tie in incomplete at this time.
|
BLD14-01578
| FIRE-Final Inspection | 4/15/2015 | 4/15/2015 | 4/15/2015 11:16:59 AM | P | PASS |
|
|
Remainder of scope of work completed, building numbers have been posted final life safety approved.
|
NAF15-00001
| INSP-Supply line flush | 4/14/2015 | 4/15/2015 | 4/15/2015 9:42:43 AM | A | FAIL |
|
|
Insufficient means provided to complete flushing.
|
BLD15-00395
| FIRE-Final Inspection | 4/14/2015 | 4/15/2015 | 4/15/2015 12:00:00 AM | A | CANC |
|
|
Larry Phone #: ###-####
|
FIR13-00142
| INSP-Final Inspection | 4/14/2015 | 4/15/2015 | 4/14/2015 3:18:27 PM | A | PASS |
|
|
Final walk through completed. Verified functional flow switch. Contractor to replace missing echeons/patch hole at mechanical closets adjacent to riser room, and to post sign at riser room door per review notes.
|