Inspections for the day of: Wednesday, April 16, 2003.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00087 INSP-Sprinkler Rough-in/Hydro4/14/20034/16/20034/16/2003 12:00:00 AMAPART
john ###-#### Hydro test for the second and third floors is OK. But items on correction notices still need corrected 4/16/2003 3:32:17 PM
BLD03-00464 FIRE-Final Inspection4/15/20034/16/20034/16/2003 12:00:00 AMAFAIL
jim; Phone #: ###-#### Repair the existing exit signs, add one exit sign per plans, add one sprinkler pendant in office 138. Per Bill Alexander no permit required for adding the one pendant 4/16/2003 9:49:10 AM
BLD02-02471 FIRE-Conference4/15/20034/16/20034/16/2003 12:00:00 AMACANC
conference was set up by the plumbing contractor . He wanted to know how to install the fire caulking for his plumbing pipe penatrations. I spoke to Dennis with Meridian Plumbling and told him to install it per the manufacturers recommendations and also gave him Russ Owens phone number 4/16/2003 4:20:03 PM
FIR02-00359 INSP-Conference4/16/20034/16/20034/16/2003 12:00:00 AMADONE
I met with mechanical engineer Bob Tikker and architect Marv Merkal and discussed the placement of the duct smoke detectors on units 1, 2 and 3. They have decided to stick with the UMC code and provide the duct smoke detectors on the supply side of these units
BLD02-02945 FIRE-Final Inspection4/16/20034/16/20034/16/2003 12:00:00 AMPPASS
jack; Phone #: ###-#### Life safety finaled for racks. No product is on site for verification of quantity 4/16/2003 2:42:10 PM
FIR03-00087 INSP-Sprinkler Rough-in4/16/20034/16/20034/16/2003 12:00:00 AMPFAIL
Provide fire caulking at the 2" penatration into the warehouse, provide the correct QR pendant in the 2nd floor office and provide the 4 way EQ bracing on the second floor main just before the wall penatration into the warehouse
FIR03-00087 INSP-Sprinkler Rough-in/Hydro4/16/20034/16/20034/16/2003 12:00:00 AMPFAIL
Provide city approved resubmitted plans showing all the piping changes. This deficiancy need to be added to the other inspection report for this project for this day