FIR07-00253
| INSP-Final Inspection | 4/16/2007 | 4/16/2007 | 4/16/2007 8:15:02 PM | P | PASS |
|
|
Fire sprinkler work passed final inspection.
|
BLD07-00138
| FIRE-Final Inspection | 4/16/2007 | 4/16/2007 | 4/16/2007 8:13:22 PM | P | FAIL |
|
|
Missing exit signs at two locations as indicated on approved plans, emergency lighting is not provided at several locations.
|
FIR06-00199
| INSP-Final Inspection | 4/13/2007 | 4/16/2007 | 4/16/2007 8:10:51 PM | P | FAIL |
|
|
Strobe notification devices at intermittent areas failed to function properly during alarm testing.
|
FIR07-00271
| INSP-Final Inspection | 4/16/2007 | 4/16/2007 | 4/16/2007 8:07:13 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
BLD07-00767
| FIRE-Final Inspection | 4/13/2007 | 4/16/2007 | 4/16/2007 8:04:29 PM | A | PASS |
|
|
Fire life safety finaled.
|
BLD05-01462
| FIRE-Final Inspection | 4/13/2007 | 4/16/2007 | 4/16/2007 11:55:20 AM | A | FAIL |
|
|
Missing required signage at the main entry/exit, one emergency light is not yet installed, need to verifiy adjacent exit discharge light will cover the back exterior exit way sufficiently, provide 2nd pc. canopies for two FS pendednts and remove plastic travel cap on one head in the storage room.
|