FIR07-00253 INSP-Final Inspection4/16/20074/16/20074/16/2007 8:15:02 PMPPASS
Fire sprinkler work passed final inspection.
BLD07-00138 FIRE-Final Inspection4/16/20074/16/20074/16/2007 8:13:22 PMPFAIL
Missing exit signs at two locations as indicated on approved plans, emergency lighting is not provided at several locations.
FIR06-00199 INSP-Final Inspection4/13/20074/16/20074/16/2007 8:10:51 PMPFAIL
Strobe notification devices at intermittent areas failed to function properly during alarm testing.
FIR07-00271 INSP-Final Inspection4/16/20074/16/20074/16/2007 8:07:13 PMPPASS
Fire alarm permit finaled.
BLD07-00767 FIRE-Final Inspection4/13/20074/16/20074/16/2007 8:04:29 PMAPASS
Fire life safety finaled.
BLD05-01462 FIRE-Final Inspection4/13/20074/16/20074/16/2007 11:55:20 AMAFAIL
Missing required signage at the main entry/exit, one emergency light is not yet installed, need to verifiy adjacent exit discharge light will cover the back exterior exit way sufficiently, provide 2nd pc. canopies for two FS pendednts and remove plastic travel cap on one head in the storage room.