Inspections for the day of: Friday, April 16, 2010.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00004 INSP-Final Inspection4/16/20104/16/20104/16/2010 4:38:01 PMPPART
Noted foil at one upright head below the new stairs to be removed, provide verification of a current annual inspection for the exisitng sprinkler system. Remainder of new installation is satisfactory.
FIR07-01041 INSP-Final Inspection4/16/20104/16/20104/16/2010 4:33:39 PMPPASS
Scope of fire sprinkler permit work finaled.
BLD08-00508 BLD-Aging Inspection4/16/20104/16/20104/16/2010 2:51:22 PMPDONE
On site visit with Reed regarding items needed for final, project completion schedule and project related fire sprinkler and alarm work.
BLD10-00406 FIRE-Final Inspection4/16/20104/16/20104/16/2010 2:08:17 PMPPASS
Craig Inspection requested from web by: Craig Brown Phone #: ###-####
BLD10-00669 FIRE-Final Inspection4/16/20104/16/20104/16/2010 2:07:31 PMPPASS
Life safety reinspection passed, corrections field verified okay.
BLD09-02291 FIRE-Final Inspection4/16/20104/16/20104/16/2010 2:06:15 PMAFAIL
Access control doors are not in compliance with the functional aspects of item #3 per IFC 1008.1.3.4- Push to exit button must interrupt power for 30 sec. upon activation.
BLD09-02031 FIRE-Final Inspection4/16/20104/16/20104/16/2010 2:00:44 PMAFAIL
C/N items are not finished, discussed issues on site with tenant. Scheduled for reinspection.
BLD09-01039 FIRE-Final Inspection4/16/20104/16/20104/16/2010 1:58:41 PMAPASS
Final inspection passed, fire life safety finaled.
FIR10-00075 INSP-Final Inspection4/16/20104/16/20104/16/2010 1:57:22 PMAPASS
UG fire supply line permit work is complete, final approved.
FIR07-00019 INSP-Final Inspection4/14/20104/16/20104/16/2010 7:17:15 AMPCANC
Brad of SG will meet Forest in the Lobby @ 1:30 pm Inspection requested from web by: Brad Bettencourt Phone #: ###-#### Inspection cancelled from web by: Brad Bettencourt
FIR06-00102 INSP-Final Inspection4/14/20104/16/20104/16/2010 7:17:10 AMPCANC
Brad of SG will meet Forest in lobby @ 1:30pm Inspection requested from web by: Brad Bettencourt Phone #: ###-#### Inspection cancelled from web by: Brad Bettencourt