Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00075 INSP-Final Inspection4/15/20144/16/20144/16/2014 4:09:45 PMPPART
Final pending the addition of two smoke detectors to complete full area coverage, need to post documents cabinet per NFPA 72, provide as-builts for modifications. Heat detectors not tested at this time. Items tested today include FACP, RA, occupant notification, manual pull stations, smoke detection, and offsite monitoring,
BLD14-00332 FIRE-Final Inspection4/15/20144/16/20144/16/2014 2:07:53 PMAPASS
Fire life safety passed. Contractor to repair two existing EM lights prior to structural final as discussed.
FIR14-00152 INSP-Final Inspection4/16/20144/16/20144/16/2014 2:05:36 PMPPASS
Remainder of permit work completed. Final walkthrough passed. Permit finaled.
BLD14-00220 FIRE-Final Inspection4/15/20144/16/20144/16/2014 11:48:31 AMAPASS
Noted correction items verified. Fire life safety passed.
BLD14-00332 FIRE-Alarm Testing4/15/20144/16/20144/16/2014 11:15:56 AMADONE
FIR13-00713 INSP-Sprinkler Rough-in4/15/20144/16/20144/16/2014 11:15:29 AMAPART
Completed inspection for tenting and insulation at the south building third floor- Okay to cover after adjustments to one area above the kitchen in the north end unit.