Inspections for the day of: Thursday, April 16, 2015.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00800 ELE-Aging Inspection4/16/20154/16/20154/21/2015 7:04:21 AM CANC
too busy
ELE15-00790 Final4/16/20154/16/20154/16/2015 3:41:18 PMPPASS
Contact Chris Husted with any Electrical questions ###-####. Thank you Phone #: ###-#### Inspection requested via web by Lori Stout Final ok
ELE14-03457 Final4/16/20154/16/20154/16/2015 3:23:30 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE15-00601 Electrical Rough-In4/16/20154/16/20154/16/2015 2:45:23 PMPPART
Ceiling Inspection please Phone #: ###-#### Inspection requested via web by Celinda Winters Bathroom entrances from store not ready. Bathroom hardlids rough in ok cover
ELE15-01015 Electrical Rough-In4/16/20154/16/20154/16/2015 2:12:01 PMPPASS
We are requesting a wall rough-in inspections for Bldg. 2L IDF and Focus Rooms for today 4/16/15 in the afternoon. Our onsite contact is Rich @ ###-####. Thank you, Phone #: ###-#### Inspection requested via web by Clint Tate For walls noted rough in ok cover
ELE15-01051 Electrical Rough-In4/16/20154/16/20154/16/2015 1:21:33 PMPPASS
Access is down side gate work done in basement. Please call to insure access. Thanks Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Rough in ok cover
ELE14-03156 Final4/16/20154/16/20154/16/2015 12:54:39 PMPFAIL
Garage code 0500. Corrections are complete. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov Missed upstairs bed closet luminaire top of stairs straight ahead. 410.16- All closet luminaires shall have enclosed lamps
ELE13-00791 ELE-Aging Inspection4/16/20154/16/20154/16/2015 11:35:10 AM DONE
Drove by and inspected
ELE13-00791 Final4/16/20154/16/20154/16/2015 11:34:56 AMPPASS
UL listing confirmed. Final ok
ELE15-01022 Final4/15/20154/16/20154/16/2015 10:09:03 AMAFAIL
Wire new AC Phone #: ###-#### Inspection requested via web by Barbara Szurgot Unit 102 is correct unit. Asked contractor to fix unit number before final. 334.12(B)- NM cable shall not be installed in a damp location.
440.52- Overcurrnt protection shall ot exceed rating on nameplate.
ELE15-01023 Final4/15/20154/16/20154/16/2015 10:03:02 AMAFAIL
Wire new AC Phone #: ###-#### Inspection requested via web by Barbara Szurgot 334.12(B)- NM cable shall not be installed in a damp location.
440.52- Over current protection shall not exceed rating on nameplate.
ELE15-00383 Final4/15/20154/16/20154/16/2015 9:18:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Spencer McLean Final ok
ELE15-00383 Electrical Rough-In4/15/20154/16/20154/16/2015 9:18:00 AMACANC
Phone #: ###-#### Inspection requested via web by Spencer McLean Needed final inspection only.
ELE15-01040 Electrical Rough-In4/15/20154/16/20154/16/2015 9:03:06 AMAPASS
Phone #: ###-#### Inspection requested via web by Spencer McLean North entrance 1st office on left. Wall rough in ok cover
ELE15-00993 Permanent Service4/16/20154/16/20154/16/2015 8:24:46 AMAPASS
Just need a service inspection for home the power has been disconnected for over a year Phone #: ###-#### Inspection requested via web by Jerry Moore p/s u/g n ok
ELE15-00993 Final4/16/20154/16/20154/16/2015 8:24:30 AMPFAIL
Just need a service inspection for home the power has been disconnected for over a year Phone #: ###-#### Inspection requested via web by Jerry Moore 408.4- Each circuit shall be identified. Circuit directory shall be completed.
352.30(A)- Service lateral shall be secured within 3' of meter.
Left correction notice