Inspections for the day of: Monday, April 16, 2018.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD17-02932 FIRE-Final Inspection4/16/20184/16/20184/16/2018 4:00:15 PMPFAIL
Fire extinguishers are mounted to high, extinguishers need to be lowered to 48inches or below. Provide signage for fire sprinkler riser room/FACP. Repair exit discharge emergency lighting, exterior emergency lights did not work on secondary power supply.
FIR17-00734 INSP-Final Inspection4/16/20184/16/20184/16/2018 3:57:46 PMPPASS
Final fire sprinkler inspection complete.
FIR17-00734 INSP-Sprinkler Rough-in/Hydro4/16/20184/16/20184/16/2018 3:57:09 PMPDONE
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.
FIR17-00734 INSP-Sprinkler Rough-in4/16/20184/16/20184/16/2018 3:56:22 PMPPASS
Rough to cover inspection for overhead fire sprinkler piping complete.
FIR18-00217 INSP-Final Inspection4/13/20184/16/20184/16/2018 3:54:40 PMPPASS
Final fire alarm inspection complete.
FIR17-00468 INSP-Conference4/16/20184/16/20184/16/2018 2:42:41 PMPDONE
Fire sprinkler conference complete.
BLD17-02966 FIRE-Final Inspection4/16/20184/16/20184/16/2018 1:46:16 PMPPASS
No fire sprinklers, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work complete.
FIR17-00364 INSP-Alarm Testing4/16/20184/16/20184/16/2018 12:08:51 PMPDONE
Fire alarm testing for room 118 complete
FIR18-00016 INSP-Final Inspection4/16/20184/16/20184/16/2018 12:08:09 PMPPASS
Final fire sprinkler inspection for area of work complete.
FIR17-00592 INSP-Final Inspection4/13/20184/16/20184/16/2018 11:53:38 AMAPASS
Final fire alarm inspection for area of work complete.
FIR17-00740 INSP-Final Inspection4/13/20184/16/20184/16/2018 11:53:22 AMAPASS
Final fire alarm inspection for area of work complete.
FIR17-00317 INSP-Sprinkler Rough-in4/16/20184/16/20184/16/2018 10:42:15 AMAPASS
Rough to cover inspection for remaining overhead fire sprinkler piping in garage complete, approved for cover. Rough to cover inspection for overhead fire sprinkler piping in trash shoot room complete, approved for cover.
FIR17-00317 INSP-Sprinkler Rough-in/Hydro4/13/20184/16/20184/16/2018 10:29:09 AMADONE
Hydrostatic test witnessed for level 1 wet system and wet standpipe (Combo floor supply/standpipe has been completed) complete, no pressure loss observed at riser provided gauge.
BLD17-04616 FIRE-Final Inspection4/13/20184/16/20184/16/2018 8:49:13 AMAPASS
No fire sprinklers, smoke detector is stand-alone and not monitored, fire extinguisher is in common area with a current inspection tag. Final life fire safety inspection for area of work complete.
BLD17-02966 FIRE-Final Inspection4/14/20184/16/20184/16/2018 8:23:41 AMAFAIL
Phone number provided was not for Joe, drove to inspection location and space was locked with no access, inspection request will need to be rescheduled and a correct phone number provided.

This inspection is for fire / life / safety. Please call Joe 30 minutes in advance for access. Phone #: ###-#### Inspection requested via web by Eric Murphy