BLD17-02932
| FIRE-Final Inspection | 4/16/2018 | 4/16/2018 | 4/16/2018 4:00:15 PM | P | FAIL |
|
|
Fire extinguishers are mounted to high, extinguishers need to be lowered to 48inches or below. Provide signage for fire sprinkler riser room/FACP. Repair exit discharge emergency lighting, exterior emergency lights did not work on secondary power supply.
|
FIR17-00734
| INSP-Final Inspection | 4/16/2018 | 4/16/2018 | 4/16/2018 3:57:46 PM | P | PASS |
|
|
Final fire sprinkler inspection complete.
|
FIR17-00734
| INSP-Sprinkler Rough-in/Hydro | 4/16/2018 | 4/16/2018 | 4/16/2018 3:57:09 PM | P | DONE |
|
|
Hydrostatic test for overhead fire sprinkler piping witnessed, no pressure loss observed at riser provided gauge.
|
FIR17-00734
| INSP-Sprinkler Rough-in | 4/16/2018 | 4/16/2018 | 4/16/2018 3:56:22 PM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete.
|
FIR18-00217
| INSP-Final Inspection | 4/13/2018 | 4/16/2018 | 4/16/2018 3:54:40 PM | P | PASS |
|
|
Final fire alarm inspection complete.
|
FIR17-00468
| INSP-Conference | 4/16/2018 | 4/16/2018 | 4/16/2018 2:42:41 PM | P | DONE |
|
|
Fire sprinkler conference complete.
|
BLD17-02966
| FIRE-Final Inspection | 4/16/2018 | 4/16/2018 | 4/16/2018 1:46:16 PM | P | PASS |
|
|
No fire sprinklers, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work complete.
|
FIR17-00364
| INSP-Alarm Testing | 4/16/2018 | 4/16/2018 | 4/16/2018 12:08:51 PM | P | DONE |
|
|
Fire alarm testing for room 118 complete
|
FIR18-00016
| INSP-Final Inspection | 4/16/2018 | 4/16/2018 | 4/16/2018 12:08:09 PM | P | PASS |
|
|
Final fire sprinkler inspection for area of work complete.
|
FIR17-00592
| INSP-Final Inspection | 4/13/2018 | 4/16/2018 | 4/16/2018 11:53:38 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
|
FIR17-00740
| INSP-Final Inspection | 4/13/2018 | 4/16/2018 | 4/16/2018 11:53:22 AM | A | PASS |
|
|
Final fire alarm inspection for area of work complete.
|
FIR17-00317
| INSP-Sprinkler Rough-in | 4/16/2018 | 4/16/2018 | 4/16/2018 10:42:15 AM | A | PASS |
|
|
Rough to cover inspection for remaining overhead fire sprinkler piping in garage complete, approved for cover. Rough to cover inspection for overhead fire sprinkler piping in trash shoot room complete, approved for cover.
|
FIR17-00317
| INSP-Sprinkler Rough-in/Hydro | 4/13/2018 | 4/16/2018 | 4/16/2018 10:29:09 AM | A | DONE |
|
|
Hydrostatic test witnessed for level 1 wet system and wet standpipe (Combo floor supply/standpipe has been completed) complete, no pressure loss observed at riser provided gauge.
|
BLD17-04616
| FIRE-Final Inspection | 4/13/2018 | 4/16/2018 | 4/16/2018 8:49:13 AM | A | PASS |
|
|
No fire sprinklers, smoke detector is stand-alone and not monitored, fire extinguisher is in common area with a current inspection tag. Final life fire safety inspection for area of work complete.
|
BLD17-02966
| FIRE-Final Inspection | 4/14/2018 | 4/16/2018 | 4/16/2018 8:23:41 AM | A | FAIL |
|
|
Phone number provided was not for Joe, drove to inspection location and space was locked with no access, inspection request will need to be rescheduled and a correct phone number provided.
This inspection is for fire / life / safety. Please call Joe 30 minutes in advance for access. Phone #: ###-#### Inspection requested via web by Eric Murphy
|