Inspections for the day of: Thursday, April 17, 1997.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMarv Burrus
TitleELE
Phone #340-1297
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE97-00659 INSP - Permanent service4/16/19974/17/19974/17/1997 12:00:00 AMACANC
04/17/97 403 - ALREADY INSPECTED BY JFRANK ON 04-16-97...MB
ELE97-01146 INSP - Permanent service4/16/19974/17/19974/17/1997 12:00:00 AMAFAIL
04/17/97 403 - NEC: 250-53(A)&(B). ELECTRODE SHALL BE CONNECTED AT SERV ENCLOSURES. (B) MAIN BONDING JUMPER SHALL BE USED TO CONNECT TO SERVICE DISCONNECT AND EACH SERVICE PANEL...MB
ELE97-01178 INSP - Electrical Rough-In4/17/19974/17/19974/17/1997 12:00:00 AMPPART
04/17/97 403 - PARCIAL ROUGH-IN HOME AFTER 2:30 P.M. INTERIOR NORTH WALL...MB
ELE97-01215 INSP - Ele Rough-In/Perm Svc4/17/19974/17/19974/17/1997 12:00:00 AMPPASS
04/17/97 403 - 12 ROOMS A/C 100 AMPS
ELE97-01218 INSP - Electrical Rough-In4/17/19974/17/19974/17/1997 12:00:00 AMPPASS
04/17/97 403 - OLD FIRST SECURITY BUILDING-LIGHTING ON THE EXTERIOR OF BUILDING.$10,000.00-BLD96-2136 BUILDING `B'; OUTSIDE ENTRY LIGHTING...MB
ELE97-00977 INSP - Electrical Rough-In4/17/19974/17/19974/17/1997 12:00:00 AMPPASS
04/17/97 403 -
ELE96-02840 INSP - Final4/17/19974/17/19974/17/1997 12:00:00 AMPCANC
04/17/97 403 - CONTRACTORS REQUEST...MB
ELE96-03880 INSP - Final4/16/19974/17/19974/17/1997 12:00:00 AMPNR
04/17/97 403 - WILL RESCHEDULE...MB