ELE05-02003
| ELE-Aging Inspection | 4/17/2006 | 4/17/2006 | 4/17/2006 3:59:32 PM | | NR |
|
|
stooped at site wsuc
|
ELE06-01198
| Rough-In Permanent Service | 4/17/2006 | 4/17/2006 | 4/17/2006 3:27:34 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/17/2006 at 8:18:26 AM. Contact: ###-####. nail plates, strap MC within 12" of reccess fixtures, ID meter and tennant space
|
ELE06-01199
| Rough-In Permanent Service | 4/17/2006 | 4/17/2006 | 4/17/2006 3:26:30 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/17/2006 at 8:17:36 AM. Contact: ###-####. corr. called needs nail plates and strap MC within 12" of reccess fixtures, ID meter and tennant space
|
ELE06-01200
| Rough-In Permanent Service | 4/17/2006 | 4/17/2006 | 4/17/2006 3:25:17 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/17/2006 at 8:16:38 AM. Contact: ###-####. corr. called needs nail plates, strap MC within 12" of reccess fixtures, ID meter and tennant
|
ELE06-01197
| Rough-In Permanent Service | 4/17/2006 | 4/17/2006 | 4/17/2006 3:24:03 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/17/2006 at 8:15:37 AM. Contact: ###-####. corr. called 300.4 nail plates,strap MC within 12" reccess fixtures, needs meter ID, and suite # for tennant
|
ELE06-01141
| Permanent Service | 4/17/2006 | 4/17/2006 | 4/17/2006 2:02:20 PM | P | FAIL |
|
|
toby Internet Inspection Request from: Tyler Bowen corr. not made and not ready
|
ELE06-01142
| Electrical Rough-In | 4/17/2006 | 4/17/2006 | 4/17/2006 12:59:32 PM | P | PART |
|
|
underground Internet Inspection Request from: Tyler Bowen u/g ok still needs equipotential grid
|
ELE06-01300
| Conference | 4/14/2006 | 4/17/2006 | 4/17/2006 11:48:32 AM | A | DONE |
|
|
###-#### - lars Note: please call 1/2 hr
|
ELE06-00974
| Final | 4/17/2006 | 4/17/2006 | 4/17/2006 10:19:04 AM | A | PASS |
|
|
Homeowner will be home. She has asked that you enter through the gate on the South side and through the garage man door for the panel and the sliding glass door in back for the bedroom.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas
|
ELE06-01141
| Final | 4/14/2006 | 4/17/2006 | 4/17/2006 9:43:46 AM | A | FAIL |
|
|
###-#### - toby corr. called 250.8 no sms, 312.5 needs conn for all cables and conductors, 310.15 derate at 50%, 250.52&104 grd within 5 ft of u/g pipe, bond hot and cold.110.26(F)(2) remove bush in front of p/s, 240.24 highest breaker position over 6ft7", 250.64(C) no splice allowed in GEC also remove it from raceway and jbox shall not ID 6 or smaller grds and neuts, cow
|
ELE06-01271
| Final | 4/13/2006 | 4/17/2006 | 4/17/2006 8:52:22 AM | A | PASS |
|
|
tom - ###-#### ok
|