Inspections for the day of: Monday, April 17, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02003 ELE-Aging Inspection4/17/20064/17/20064/17/2006 3:59:32 PM NR
stooped at site wsuc
ELE06-01198 Rough-In Permanent Service4/17/20064/17/20064/17/2006 3:27:34 PMPFAIL
Scheduled by a contractor via Hello! on 4/17/2006 at 8:18:26 AM. Contact: ###-####. nail plates, strap MC within 12" of reccess fixtures, ID meter and tennant space
ELE06-01199 Rough-In Permanent Service4/17/20064/17/20064/17/2006 3:26:30 PMPFAIL
Scheduled by a contractor via Hello! on 4/17/2006 at 8:17:36 AM. Contact: ###-####. corr. called needs nail plates and strap MC within 12" of reccess fixtures, ID meter and tennant space
ELE06-01200 Rough-In Permanent Service4/17/20064/17/20064/17/2006 3:25:17 PMPFAIL
Scheduled by a contractor via Hello! on 4/17/2006 at 8:16:38 AM. Contact: ###-####. corr. called needs nail plates, strap MC within 12" of reccess fixtures, ID meter and tennant
ELE06-01197 Rough-In Permanent Service4/17/20064/17/20064/17/2006 3:24:03 PMPFAIL
Scheduled by a contractor via Hello! on 4/17/2006 at 8:15:37 AM. Contact: ###-####. corr. called 300.4 nail plates,strap MC within 12" reccess fixtures, needs meter ID, and suite # for tennant
ELE06-01141 Permanent Service4/17/20064/17/20064/17/2006 2:02:20 PMPFAIL
toby Internet Inspection Request from: Tyler Bowen corr. not made and not ready
ELE06-01142 Electrical Rough-In4/17/20064/17/20064/17/2006 12:59:32 PMPPART
underground Internet Inspection Request from: Tyler Bowen u/g ok still needs equipotential grid
ELE06-01300 Conference4/14/20064/17/20064/17/2006 11:48:32 AMADONE
###-#### - lars Note: please call 1/2 hr
ELE06-00974 Final4/17/20064/17/20064/17/2006 10:19:04 AMAPASS
Homeowner will be home. She has asked that you enter through the gate on the South side and through the garage man door for the panel and the sliding glass door in back for the bedroom.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas
ELE06-01141 Final4/14/20064/17/20064/17/2006 9:43:46 AMAFAIL
###-#### - toby corr. called 250.8 no sms, 312.5 needs conn for all cables and conductors, 310.15 derate at 50%, 250.52&104 grd within 5 ft of u/g pipe, bond hot and cold.110.26(F)(2) remove bush in front of p/s, 240.24 highest breaker position over 6ft7", 250.64(C) no splice allowed in GEC also remove it from raceway and jbox shall not ID 6 or smaller grds and neuts, cow
ELE06-01271 Final4/13/20064/17/20064/17/2006 8:52:22 AMAPASS
tom - ###-#### ok