Inspections for the day of: Thursday, April 17, 2008.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMike Kinnear
TitleELE-INSPECTOR
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-00373 Electrical Rough-In4/17/20084/17/20084/17/2008 4:54:45 PMPPASS
john Phone #: ###-#### ok cover under slab conduit anop
ELE08-00692 Rough-In Permanent Service4/17/20084/17/20084/17/2008 4:43:23 PMPFAIL
###-#### Internet Inspection Request from: Todd Holbrook corrections Nec250.64(C) grounding electrode conductor shall be continuous from one panel to the other & 210.52(A)(2) wall spacing railings for stairwell 1st floor
ELE08-00131 Final4/17/20084/17/20084/17/2008 2:50:29 PMAPASS
ok final wall signs
ELE08-00638 Final4/17/20084/17/20084/17/2008 2:49:46 PMPPASS
bill Phone #: ###-#### ok final
ELE08-00466 Final4/17/20084/17/20084/17/2008 12:18:13 PMPPART
Phone #: ###-#### Internet Inspection Request from: Alan Lusk counters not installed yet wiring not completed in them note check the rest of the area it is ok
ELE08-00939 Electrical Rough-In4/16/20084/17/20084/17/2008 11:30:46 AMAPASS
Key in black mail box Phone #: ###-#### Internet Inspection Request from: Alan Lusk ok cover walls only
ELE08-00893 Rough-In Permanent Service4/16/20084/17/20084/17/2008 10:31:06 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok cover ri p/s u/g n ok note t/w general contractor address not correct & t/w electrical contractor regarding addressing & rm count there are 41 rms not 10 for the four plex they need to call office & fix it
ELE07-02739 Final4/17/20084/17/20084/17/2008 8:54:00 AMANR
todd Phone #: ###-#### not ready conf needs flor. light in basement closet, inuse covers outside outlets, & panel labled
ELE07-03950 Rough-In Permanent Service4/16/20084/17/20084/17/2008 8:27:49 AMAPASS
Service grounding for shell and core Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok grounding & bonding p/s u/g n ok note services ok for house panel ( panel H) & maintainance panel (panel M)