FIR12-00034
| INSP-Final Inspection | 4/17/2012 | 4/17/2012 | 4/19/2012 5:21:59 PM | P | PART |
|
|
Final pending 24 hr. test per NFPA 13 2010 24.2.2.1, need to seal or lock the trim valve to the waterflow pressure switch per IFC sec. 903.4 (7).
|
FIR12-00043
| INSP-Final Inspection | 4/17/2012 | 4/17/2012 | 4/19/2012 4:59:45 PM | P | PASS |
|
|
Scope of work passed field testing.
|
FIR11-00236
| INSP-Final Inspection | 4/17/2012 | 4/17/2012 | 4/19/2012 4:56:50 PM | P | PASS |
|
|
C/N items verified. Fire alarm permit finaled.
|
BLD11-00818
| FIRE-Final Inspection | 4/17/2012 | 4/17/2012 | 4/19/2012 4:55:35 PM | A | PART |
|
|
TCO only for "phase one" at portions of the sub-fab, photo bay and mechanical areas per agreement on record.
|
FIR12-00033
| INSP-Conference | 4/17/2012 | 4/17/2012 | 4/19/2012 4:44:47 PM | A | DONE |
|
|
|
FIR11-00575
| INSP-Final Inspection | 4/17/2012 | 4/17/2012 | 4/19/2012 4:44:13 PM | P | PART |
|
|
|
FIR12-00033
| INSP-Alarm Testing | 4/17/2012 | 4/17/2012 | 4/17/2012 7:51:12 AM | A | FAIL |
|
|
Correction items at the basement lab area include; remove or relocate the existing manual pull station, existing notification appliance does not provide adequate coverage for the locker area.
|