BLD13-00674
| FIRE-Final Inspection | 4/15/2013 | 4/17/2013 | 4/17/2013 2:40:31 PM | P | FAIL |
|
|
Need to provide approved door hardware at several locations, remove or disable manual thumbturns at required exit doors, post "door to remain..." signage at the main entry/exit, min. rated fire extinguisher is 2A10BC.
|
FIR12-00550
| INSP-Sprinkler Rough-in | 4/16/2013 | 4/17/2013 | 4/17/2013 2:37:02 PM | A | PART |
|
|
Reference dated and clouded notes on approved plan for locations in phase two approved for cover.
|
BLD13-00755
| FIRE-Final Inspection | 4/17/2013 | 4/17/2013 | 4/17/2013 2:34:12 PM | A | FAIL |
|
|
Correction items include; repair two exit signs, relocate one exit sign, reverse hardware at two locations, provide approved hardware at the east and west office area exit doors.
|