Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00794 ELE-Aging Inspection4/17/20154/17/20154/24/2015 3:34:39 PM DONE
Drove by and inspected
ELE13-00819 ELE-Aging Inspection4/17/20154/17/20154/21/2015 7:04:40 AM CANC
too busy
ELE15-01002 Electrical Rough-In4/16/20154/17/20154/17/2015 3:38:35 PMPPART
Please call Kyle Dillon ###-#### 30 Mins. prior to arrival. Thanks! Phone #: ###-#### Inspection requested via web by MIKE HAGERTY Interior wall except break room area not ready. Rest rough in ok cover
ELE14-02819 Permanent Service4/17/20154/17/20154/17/2015 2:51:48 PMPFAIL
Phone #: ###-#### Inspection requested via web by kendall bender
110.24- AIC rating shall be calculated and posted with available fault current and date calculated prior to permanent service.
240.24(A)- Overcurrent devices shall be installed so the operating handle in it's highest point does not exceed 6'7".
ELE15-00929 Rough-In Permanent Service4/17/20154/17/20154/17/2015 2:07:13 PMPPASS
Cody is the contact on site at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
ELE15-00601 Electrical Rough-In4/17/20154/17/20154/17/2015 1:40:03 PMPPASS
Ceiling inspection please Phone #: ###-#### Inspection requested via web by Celinda Winters Bath entrance on retail side hardlid rough in ok cover
ELE15-00596 Final4/17/20154/17/20154/17/2015 1:26:12 PMPPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
ELE14-02963 Final4/16/20154/17/20154/17/2015 1:13:00 PMAFAIL
Final Electrical Inspection Phone #: ###-#### Inspection requested via web by Louis Keller 210.8-Bathroom receptacles in light fixtures shall have GFCI protection or be removed.
422.25-Disconnecting means shall be provided for well.
Unused openings shall be closed. Shop panel.
408.4- Shop panel circuit directory shall be completed.
ELE15-01018 Electrical Rough-In4/16/20154/17/20154/17/2015 9:52:48 AMAPASS
Christian Phone #: ###-#### Underground from temp pole by shop to house rough in ok cover
ELE15-00463 Final4/16/20154/17/20154/17/2015 9:24:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Rhonda Zamagni Receptacle mounted on sign base GFCI protected from outlet in island to south confirmed by contractor. Final ok
ELE13-01058 Electrical Rough-In4/17/20154/17/20154/17/2015 9:03:57 AMAPASS
rough in on warehouse.
we shoudl arrive around 9am. Phone #: ###-#### Inspection requested via web by Tim Dunlop UL listing and disconnecting means confirmed. Shanging high bays to flourescent with motion. Rough in ok
ELE15-01023 Final4/16/20154/17/20154/17/2015 8:34:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
ELE15-01022 Final4/16/20154/17/20154/17/2015 8:34:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
ELE15-00596 Final4/16/20154/17/20154/17/2015 8:20:15 AMAFAIL
Key in front outlet for entry Phone #: ###-#### Inspection requested via web by TOM BICANDI 210.8- All 120 volt receptacle outlets located within 6' of sink shall have GFCI protection. Back side of kitchen sink.
314.20- Boxes with non-combustable surface shall not be recessed more than 1/4" with out box extender. boxes in tile.
Wire AC unit