ELE13-00794
| ELE-Aging Inspection | 4/17/2015 | 4/17/2015 | 4/24/2015 3:34:39 PM | | DONE |
|
|
Drove by and inspected
|
ELE13-00819
| ELE-Aging Inspection | 4/17/2015 | 4/17/2015 | 4/21/2015 7:04:40 AM | | CANC |
|
|
too busy
|
ELE15-01002
| Electrical Rough-In | 4/16/2015 | 4/17/2015 | 4/17/2015 3:38:35 PM | P | PART |
|
|
Please call Kyle Dillon ###-#### 30 Mins. prior to arrival. Thanks! Phone #: ###-#### Inspection requested via web by MIKE HAGERTY Interior wall except break room area not ready. Rest rough in ok cover
|
ELE14-02819
| Permanent Service | 4/17/2015 | 4/17/2015 | 4/17/2015 2:51:48 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 110.24- AIC rating shall be calculated and posted with available fault current and date calculated prior to permanent service. 240.24(A)- Overcurrent devices shall be installed so the operating handle in it's highest point does not exceed 6'7".
|
ELE15-00929
| Rough-In Permanent Service | 4/17/2015 | 4/17/2015 | 4/17/2015 2:07:13 PM | P | PASS |
|
|
Cody is the contact on site at ###-#### Phone #: ###-#### Inspection requested via web by Tracy Robertson Rough in ok cover p/s u/g n ok
|
ELE15-00601
| Electrical Rough-In | 4/17/2015 | 4/17/2015 | 4/17/2015 1:40:03 PM | P | PASS |
|
|
Ceiling inspection please Phone #: ###-#### Inspection requested via web by Celinda Winters Bath entrance on retail side hardlid rough in ok cover
|
ELE15-00596
| Final | 4/17/2015 | 4/17/2015 | 4/17/2015 1:26:12 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI Final ok
|
ELE14-02963
| Final | 4/16/2015 | 4/17/2015 | 4/17/2015 1:13:00 PM | A | FAIL |
|
|
Final Electrical Inspection Phone #: ###-#### Inspection requested via web by Louis Keller 210.8-Bathroom receptacles in light fixtures shall have GFCI protection or be removed. 422.25-Disconnecting means shall be provided for well. Unused openings shall be closed. Shop panel. 408.4- Shop panel circuit directory shall be completed.
|
ELE15-01018
| Electrical Rough-In | 4/16/2015 | 4/17/2015 | 4/17/2015 9:52:48 AM | A | PASS |
|
|
Christian Phone #: ###-#### Underground from temp pole by shop to house rough in ok cover
|
ELE15-00463
| Final | 4/16/2015 | 4/17/2015 | 4/17/2015 9:24:24 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rhonda Zamagni Receptacle mounted on sign base GFCI protected from outlet in island to south confirmed by contractor. Final ok
|
ELE13-01058
| Electrical Rough-In | 4/17/2015 | 4/17/2015 | 4/17/2015 9:03:57 AM | A | PASS |
|
|
rough in on warehouse. we shoudl arrive around 9am. Phone #: ###-#### Inspection requested via web by Tim Dunlop UL listing and disconnecting means confirmed. Shanging high bays to flourescent with motion. Rough in ok
|
ELE15-01023
| Final | 4/16/2015 | 4/17/2015 | 4/17/2015 8:34:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
|
ELE15-01022
| Final | 4/16/2015 | 4/17/2015 | 4/17/2015 8:34:08 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
|
ELE15-00596
| Final | 4/16/2015 | 4/17/2015 | 4/17/2015 8:20:15 AM | A | FAIL |
|
|
Key in front outlet for entry Phone #: ###-#### Inspection requested via web by TOM BICANDI 210.8- All 120 volt receptacle outlets located within 6' of sink shall have GFCI protection. Back side of kitchen sink. 314.20- Boxes with non-combustable surface shall not be recessed more than 1/4" with out box extender. boxes in tile. Wire AC unit
|