ELE17-01084
| Temporary Service | 4/17/2017 | 4/17/2017 | 4/17/2017 3:57:44 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE17-01085
| Temporary Service | 4/17/2017 | 4/17/2017 | 4/17/2017 3:43:53 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE17-01082
| Rough-In Permanent Service | 4/17/2017 | 4/17/2017 | 4/17/2017 3:34:36 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|
ELE17-01021
| Rough-In Permanent Service | 4/17/2017 | 4/17/2017 | 4/17/2017 2:51:55 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Can openings in soffits do not have fire protection at time of inspection. Rest on corrections complete. Rough in ok cover p/s u/g n ok
|
ELE17-00037
| Final | 4/14/2017 | 4/17/2017 | 4/17/2017 2:12:05 PM | P | PART |
|
|
Final for Building 12 Contact Dan Hutchinson Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek 406.12 ex.2- Receptacles that are part of a luminare not required to be tamper resistant. Luminaire, swithes, and receptacles all mounted on back plate. TCO building 12 ok
|
ELE17-01021
| Rough-In Permanent Service | 4/14/2017 | 4/17/2017 | 4/17/2017 10:52:48 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Wui Zone A soffit cans not covered.
210.52(I)- Foyers over 60 sq.ft shall have a receptacle outlet installed on all walls 3' and wider. 210.70(A)(2)(b)- All exterior doors shall have an opening for illumination. Can in place wiring. 334.12- NM cable shall not be installed where subject to physical damage. Master hall hanging below ceiling. 300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" they shall be protected by nail plates. Garage east wall (3), m. shower 45 degree, m vanity 45 degree and above and secure below GFI center staple or protect.
|
ELE17-00052
| Final | 4/14/2017 | 4/17/2017 | 4/17/2017 10:29:38 AM | A | FAIL |
|
|
Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker 210.8- Drinking fountain shall have GFCI protection that is readily accessible. 210.70- Outdoor egress lighring not installed as per print.
|
ELE17-00507
| Final | 4/14/2017 | 4/17/2017 | 4/17/2017 8:33:28 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
|