Inspections for the day of: Monday, April 17, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-01084 Temporary Service4/17/20174/17/20174/17/2017 3:57:44 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE17-01085 Temporary Service4/17/20174/17/20174/17/2017 3:43:53 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE17-01082 Rough-In Permanent Service4/17/20174/17/20174/17/2017 3:34:36 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g n ok
ELE17-01021 Rough-In Permanent Service4/17/20174/17/20174/17/2017 2:51:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Can openings in soffits do not have fire protection at time of inspection. Rest on corrections complete. Rough in ok cover p/s u/g n ok
ELE17-00037 Final4/14/20174/17/20174/17/2017 2:12:05 PMPPART
Final for Building 12
Contact Dan Hutchinson
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek
406.12 ex.2- Receptacles that are part of a luminare not required to be tamper resistant. Luminaire, swithes, and receptacles all mounted on back plate.
TCO building 12 ok
ELE17-01021 Rough-In Permanent Service4/14/20174/17/20174/17/2017 10:52:48 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn

Wui Zone A soffit cans not covered.

210.52(I)- Foyers over 60 sq.ft shall have a receptacle outlet installed on all walls 3' and wider.
210.70(A)(2)(b)- All exterior doors shall have an opening for illumination. Can in place wiring.
334.12- NM cable shall not be installed where subject to physical damage. Master hall hanging below ceiling.
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" they shall be protected by nail plates. Garage east wall (3), m. shower 45 degree, m vanity 45 degree and above and secure below GFI center staple or protect.
ELE17-00052 Final4/14/20174/17/20174/17/2017 10:29:38 AMAFAIL
Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker
210.8- Drinking fountain shall have GFCI protection that is readily accessible.
210.70- Outdoor egress lighring not installed as per print.
ELE17-00507 Final4/14/20174/17/20174/17/2017 8:33:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn
Final ok