Inspections for the day of: Tuesday, April 17, 2018.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00133 INSP-Final Inspection4/17/20184/17/20184/17/2018 3:09:14 PMPFAIL
Project can be finaled when as-builts have been received by plan review.


Chris Siewert - Technician Phone #: ###-#### Inspection requested via web by John Siewert
BLD17-03533 FIRE-Final Inspection4/17/20184/17/20184/17/2018 2:55:22 PMPFAIL
Repair exit sign, provide emergency light, provide additional fire extinguisher, provide installation and testing of the fire door that meets NFPA 80, exit sign leads people to the fire door so this needs approved by the plan reviewer.

Kent Phone #: ###-####
BLD17-02932 FIRE-Final Inspection4/17/20184/17/20184/17/2018 2:47:00 PMPCANC
Greg Phone #: ###-####
BLD18-00706 FIRE-Final Inspection4/16/20184/17/20184/17/2018 2:40:21 PMACANC
call when on way (10 min out) // Justin Phone #: ###-####
BLD17-03833 FIRE-Final Inspection4/17/20184/17/20184/17/2018 2:36:53 PMPFAIL
Project is not ready for a final. Todays inspection was a conference with the electrician about the placement of exit signs and emergency lights. There were no approved plans on site so there was not much I could do. I met with one of the owners and let him know that I would not be signing off untill the aging permit FIR12-004


74 was finaled.


Dale Campbell Jr. Phone #: ###-####
FIR17-00771 INSP-Supply line flush4/17/20184/17/20184/17/2018 1:43:35 PMPPASS
The underground supply line flush passed.

Johnathon Phone #: ###-####
FIR18-00240 INSP-Sprinkler Rough-in/Hydro4/17/20184/17/20184/17/2018 1:43:01 PMPPASS
The overhead 200lb hydro on new dry system passed. The 24 hour air test was started at 1:40 with 44psi on the guage.
FIR18-00133 INSP-Final Inspection4/12/20184/17/20184/17/2018 10:54:22 AMPCANC
Zak Anderson - Technician Phone #: ###-#### >> Inspection requested via web by John Siewert Inspection cancelled from web by: John Siewert
FIR18-00024 INSP-Sprinkler Rough-in4/16/20184/17/20184/17/2018 10:11:28 AMAPART
See the city approved plans for rooms marked "ok" in red where the sprinkler piping is ok for cover. I noted two rooms on the west side that need retaining straps.

Jeff Chaney is the contact for this rough to cover inspection. Thank you for your help. Phone #: ###-#### Inspection requested via web by Stan Beus