Inspections for the day of: Friday, April 17, 2020.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-00311 Electrical Rough-In4/17/20204/17/20204/17/2020 1:32:58 PMPPASS
There was some additional underground installation that needs to be inspected. Please call Jeff with any questions at ###-####. Phone #: ###-#### Inspection requested via web by Joe McLean
Called and informed the violation of
240.24(E)- Overcurrent devices shall not be located in a bathroom. Offered a solution of creating a seperation by enclosing panel behind a door but to be careful to make sure all required work space is present at time of final as per 110.26.
Underground extension rough in ok cover.
ELE20-00366 Final4/17/20204/17/20204/17/2020 10:08:42 AMPPASS
Contractor called back and provided acces as per noted on 4-15-2020. Final ok
ELE20-01250 Electrical Rough-In4/16/20204/17/20204/17/2020 9:48:40 AMAPASS
call for access- Jose **Cleared** Phone #: ###-####
Called to have ELE attached to BLD20-00803 however system issues, unable to reach an permit tech or leave message.
Grid rough in ok cover.
ELE19-00601 Electrical Rough-In4/15/20204/17/20204/17/2020 9:30:39 AMAPASS
Ceiling cover in mens/womens first floor. Danny is the contact but will not be onsite. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level 1 bathroom hardlids rough in ok cover.
ELE20-00685 Electrical Rough-In4/16/20204/17/20204/17/2020 8:38:52 AMAPASS
Requesting 8:00 am inspection time. Actual suite location is 100 8th street. Installing 1 under canopy sign Phone #: ###-#### Inspection requested via web by Ken Olsen
Disconnecting means and listing confirmed. Rough in ok cover
ELE20-00685 Final4/17/20204/17/20204/17/2020 8:36:53 AMPPASS
Requesting 8:00 am inspection time. Actual suite location is 100 8th street. Installing 1 under canopy sign Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok