Inspections for the day of: Thursday, April 18, 2002.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR01-00462 INSP-Sprinkler Rough-in4/17/20024/18/20024/18/2002 12:00:00 AMAPART
###-#### MIKE okay to cover in several areas; need to reinpsect the sanctuary after painting to check heads 4/18/2002 4:12:29 PM
BLD01-01044 FIRE-Final Inspection4/17/20024/18/20024/18/2002 12:00:00 AMAFAIL
dick- ###-#### per rick at 8:30 labels on rated doors; access doors for smoke dampers; fire alarm plans needed; overhead door traps occupants inside when door is released by fusible links; need to test alarms; exit sign needed; penetrations in rated walls 4/18/2002 10:39:33 AM
FIR02-00074 INSP-Sprinkler Rough-in/Hydro4/17/20024/18/20024/18/2002 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 04/17/2002 at 14:38:33. Contact: ###-####.
FIR02-00123 INSP-Supply line flush4/18/20024/18/20024/18/2002 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 04/18/2002 at 10:15:48. Contact: ###-####. supply line cover only - okay to cover 4/18/2002 4:11:36 PM
FIR02-00078 INSP-Final Inspection4/18/20024/18/20024/18/2002 12:00:00 AMPPASS
Added by Inspector: 409 On 4/18/2002 6:36:56 PM
FIR02-00079 INSP-Final Inspection4/18/20024/18/20024/18/2002 12:00:00 AMPPASS
Added by Inspector: 409 On 4/18/2002 6:37:14 PM
FIR02-00045 INSP-Final Inspection4/18/20024/18/20024/18/2002 12:00:00 AMPPASS
Added by Inspector: 409 On 4/18/2002 6:37:37 PM