FIR01-00462
| INSP-Sprinkler Rough-in | 4/17/2002 | 4/18/2002 | 4/18/2002 12:00:00 AM | A | PART |
|
|
###-#### MIKE okay to cover in several areas; need to reinpsect the sanctuary after painting to check heads 4/18/2002 4:12:29 PM
|
BLD01-01044
| FIRE-Final Inspection | 4/17/2002 | 4/18/2002 | 4/18/2002 12:00:00 AM | A | FAIL |
|
|
dick- ###-#### per rick at 8:30 labels on rated doors; access doors for smoke dampers; fire alarm plans needed; overhead door traps occupants inside when door is released by fusible links; need to test alarms; exit sign needed; penetrations in rated walls 4/18/2002 10:39:33 AM
|
FIR02-00074
| INSP-Sprinkler Rough-in/Hydro | 4/17/2002 | 4/18/2002 | 4/18/2002 12:00:00 AM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 04/17/2002 at 14:38:33. Contact: ###-####.
|
FIR02-00123
| INSP-Supply line flush | 4/18/2002 | 4/18/2002 | 4/18/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 04/18/2002 at 10:15:48. Contact: ###-####. supply line cover only - okay to cover 4/18/2002 4:11:36 PM
|
FIR02-00078
| INSP-Final Inspection | 4/18/2002 | 4/18/2002 | 4/18/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 4/18/2002 6:36:56 PM
|
FIR02-00079
| INSP-Final Inspection | 4/18/2002 | 4/18/2002 | 4/18/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 4/18/2002 6:37:14 PM
|
FIR02-00045
| INSP-Final Inspection | 4/18/2002 | 4/18/2002 | 4/18/2002 12:00:00 AM | P | PASS |
|
|
Added by Inspector: 409 On 4/18/2002 6:37:37 PM
|