Inspections for the day of: Monday, April 18, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-01282 Rough-In Permanent Service4/15/20054/18/20054/18/2005 12:00:00 AMAFAIL
dean ###-#### cor. do not cover posted called 300.4(A)(1)&(D)
4/18/2005 10:35:25 AM
ELE05-01283 Rough-In Permanent Service4/15/20054/18/20054/18/2005 12:00:00 AMAFAIL
dean ###-#### cor. do not cover posted called 300.4(A)(1)&(D) 4/18/2005 10:36:08 AM
ELE05-01280 Electrical Rough-In4/15/20054/18/20054/18/2005 12:00:00 AMAPART
any questions please call Ed Scahllock; Phone #: ###-#### Internet Inspection Request from: Jeff Radford u/g for com. lines ok 4/18/2005 9:00:08 AM
ELE04-03437 Final4/15/20054/18/20054/18/2005 12:00:00 AMAPART
t/o for office area only, card signed, some equipment on foof not listed 4/18/2005 9:34:39 AM
ELE05-00741 Final4/18/20054/18/20054/18/2005 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 4/18/2005 at 7:31:01 AM. Contact: ###-####. ok 4/18/2005 8:22:07 AM
ELE05-00061 Final4/18/20054/18/20054/18/2005 12:00:00 AMPPASS
please call for access information///alan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 4/18/2005 12:41:55 PM
ELE01-02385 Final4/18/20054/18/20054/18/2005 12:00:00 AMPPASS
please call 15 min prior to inspection at ###-#### kathy ok card signed 4/18/2005 2:07:04 PM
ELE05-00854 Final4/18/20054/18/20054/18/2005 12:00:00 AMPPASS
daryl; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok 4/18/2005 2:48:38 PM
ELE05-01285 Temporary Service4/18/20054/18/20054/18/2005 12:00:00 AMPPASS
t/s only ok for now o/h rec.
ELE05-01285 Final4/15/20054/18/20054/18/2005 12:00:00 AMPCANC
Please call my cell at ###-####. Id power is shutting off pwer about 12 noon. It should take 2-3hours for the repair and then I'll need inspection to get power back on the same day. Thank you. Randy Fletcher; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher no yiolation retained,sub panel shall have grds and neutraks isolated, 4 wire branch circuir from sub panel to range, all grds and bond shall be at service equip remove from sub panel , p/s shall have required clearence,prior owner created a mess out of electrical without permit or inspection see added t/s 4/18/2005 2:05:58 PM