ELE05-01239
| Permanent Service | 4/16/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack corrections made, p/s u/g n ok 4/18/2005 10:21:50 AM
|
ELE05-01251
| Electrical Rough-In | 4/17/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | A | PASS |
|
|
Call for the door code. This is for a wall rough in inspection; Phone #: ###-#### Internet Inspection Request from: DJ Carman called contr, left survey, 330.30 cable shall be secured within 12" of box, 330.17 cable shall be protected in accordance with 300.4(D) 1 1/4" from edge of framing member. ric walls only 4/18/2005 9:40:34 AM
|
ELE05-01281
| Temporary Service | 4/15/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | A | FAIL |
|
|
mark ###-#### called contr, no answer, told builder, left corr notice, 225.22 emt conn shall be raintight listed, 314.17 gnd wire shall be protected from abrasion, 110.12(A) unused openings shall be closed 4/18/2005 8:40:48 AM
|
ELE05-01277
| Electrical Rough-In | 4/15/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | A | PASS |
|
|
bob; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ric ok bathrooms only 4/18/2005 8:07:11 AM
|
ELE05-01053
| Final | 4/15/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 4/15/2005 at 4:27:02 PM. Contact: ###-####. when I got there, 4 electricians working on a/c, switches, ceiling boxes, panel, exit lites. I looked at ceiling for cover which is ok, but panel not made up so couldn't check recpts. They were going to pull part of ckt for pos recpts, I said they needed to do all or not in order to final. I said to call for another inspection, to final. 4/18/2005 3:41:32 PM
|
ELE05-00462
| Electrical Rough-In | 4/14/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 4/14/2005 at 3:39:20 PM. Contact: ###-####. called contr, no access, looked thru window and told contr all make-up had to be done before inspection anyway. He will call back for rip when ready. All the boxes had nm cable coiled up and not made up. 4/18/2005 12:57:27 PM
|
ELE05-01190
| Final | 4/18/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | P | CANC |
|
|
CONTACT: MIKE ROBINSON U/G INSPECTION PLEASE; Phone #: ###-#### Internet Inspection Request from: Deb McCoy created new inspection for r/i u/g 4/18/2005 4:13:19 PM
|
ELE05-01291
| Temporary Service | 4/18/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | P | PASS |
|
|
dan ###-#### t/s u/g n ok 4/18/2005 2:02:10 PM
|
ELE05-01190
| Electrical Rough-In | 4/18/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | P | PASS |
|
|
ok to cover u/g so side of bldg for service area
|