Inspections for the day of: Monday, April 18, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00093 INSP-Sprinkler Rough-in/Hydro4/15/20054/18/20054/18/2005 4:16:39 PMPPART
Overhead sprinkler rough-in OK to cover, need calc. verification on 3 inch main offset at south end, need psi relief at riser for grid system.
FIR05-00154 INSP-Sprinkler Rough-in4/18/20054/18/20054/18/2005 4:11:24 PMPFAIL
Fail inspection, fire sprinkler changes in spray booth and exterior compressor room not completed.
FIR05-00084 INSP-Alarm Testing4/15/20054/18/20054/18/2005 1:12:32 PMAFAIL
Fail inspection, in-duct detectors/dampers located in upper mechanical room failed to operate properly.
BLD04-02978 FIRE-Final Inspection4/15/20054/18/20054/18/2005 1:06:17 PMAFAIL
Fail inspection. Keyed hardware is only allowed on one door. Main entry/exit has three. See building review note #14 and fire review note #6. Remove manual flush bolts from conference room doors, see bld. review note #15. Duct detectors are mounted o
FIR05-00150 INSP-Final Inspection4/15/20054/18/20054/18/2005 12:57:16 PMAPASS
Life safety finaled. Mag door locks operated properly under test conditions.
FIR04-00350 INSP-Final Inspection4/18/20054/18/20054/18/2005 12:50:55 PMAFAIL
Fire sprinkler rough-in inspection fail. Items need corrected include adding EQ brace 2nd floor south 2.5 in. main, upright too far off stair wall 2nd floor north, upright heads on two lines 2nd floor north are too low below deck.
FIR04-00811 INSP-Final Inspection4/15/20054/18/20054/18/2005 9:03:23 AMAFAIL
Contact: ###-####. Fail inspection, approved plans not available on site for review.
FIR04-00350 INSP-Sprinkler Rough-in/Hydro4/18/20054/18/20054/18/2005 12:00:00 AMPPASS
Overhead hydro. test OK.
FIR05-00093 INSP-Sprinkler Rough-in/Hydro4/18/20054/18/20054/18/2005 12:00:00 AMPPASS
Overhead hydro test passed.