FIR05-00121
| INSP-Sprinkler Rough-in/Hydro | 4/18/2005 | 4/18/2005 | 4/18/2005 4:33:50 PM | P | FAIL |
|
|
Multiple branchlines have been relocated and now appear to exceed 99 sq.ft. max. spacing. Provide verification that afcon 303 rings have been used for the trapeze hangers. Provide flexible cplings at the top and bottom of the risers at the inracks. Provid
|
FIR05-00216
| INSP-Final Inspection | 4/15/2005 | 4/18/2005 | 4/18/2005 4:25:51 PM | A | PART |
|
|
inspection done by sam. temp given by fire dept.
|
FIR05-00207
| INSP-Final Inspection | 4/18/2005 | 4/18/2005 | 4/18/2005 4:08:24 PM | P | PASS |
|
|
fire alarm finaled
|
FIR05-00102
| INSP-Final Inspection | 4/18/2005 | 4/18/2005 | 4/18/2005 4:07:35 PM | P | PASS |
|
|
Fire alarm finaled
|
BLD04-02886
| FIRE-Final Inspection | 4/15/2005 | 4/18/2005 | 4/18/2005 1:52:59 PM | P | PART |
|
|
###-#### - peter A temporary occupancy was given with Dave Lokker's permission until the correct remote annunciators for the duct smoke detectors afor the re installed and tested. Contractor provide cut sheet showind ada compliance for the thumbturns.
|
FIR04-00656
| INSP-Conference | 4/15/2005 | 4/18/2005 | 4/18/2005 1:02:23 PM | A | DONE |
|
|
to discuss fire damper access in pool room///calvin ###-#### Told hvac contractor that he could either install one large access panel or three smaller ones at the fire dampers for serviceing them. Per him the ceiling where the access doors are to be ins
|
MIS05-00046
| FIR-Final | 4/15/2005 | 4/18/2005 | 4/18/2005 1:00:52 PM | A | PART |
|
|
david-- ###-#### --A temporary occupancy was given. Need to remove thumbturn from the main entry/exit. Keyed is ok. Remove the manual flush bolts from the main entry. Automatic flush bolts are ok to use. Remove the thumbturn from the southeast exit. Provi
|
BLD04-02016
| FIRE-Final Inspection | 4/18/2005 | 4/18/2005 | 4/18/2005 12:57:55 PM | P | PASS |
|
|
Fire life safety finaled
|
FIR05-00183
| INSP-Sprinkler Rough-in | 4/15/2005 | 4/18/2005 | 4/18/2005 9:00:02 AM | A | FAIL |
|
|
###-#### No responce from Grinnell when I called and can not find approved sprinkler plans at job site
|
FIR05-00121
| INSP-Conference | 4/15/2005 | 4/18/2005 | 4/18/2005 8:18:13 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 4/15/2005 at 2:18:57 PM. Contact: ###-####. No body at the site for the conference. I called Treasure Valley's office prior to showing up but the lady who answered the phone wasn't sure who I needed to talk
|
BLD05-00601
| FIRE-Final Inspection | 4/15/2005 | 4/18/2005 | 4/18/2005 8:06:15 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 4/15/2005 at 10:30:02 AM. Contact: ###-####.
|
BLD04-02940
| FIRE-Final Inspection | 4/15/2005 | 4/18/2005 | 4/18/2005 8:04:22 AM | A | PASS |
|
|
Fire life safety finaled
|
FIR05-00093
| INSP-Final Inspection | 4/15/2005 | 4/18/2005 | 4/18/2005 7:42:41 AM | A | CANC |
|
|
###-#### Jim Inspection cancelled from web by: Alicia Pauley
|
FIR05-00013
| INSP-Final Inspection | 4/18/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | P | PASS |
|
|
Permit finaled
|
FIR05-00070
| INSP-Final Inspection | 4/18/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | P | PASS |
|
|
Permit finaled
|
FIR04-00698
| INSP-Final Inspection | 4/18/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled
|
FIR05-00207
| INSP-Final Inspection | 4/18/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | P | PASS |
|
|
Fire alarm finaled
|
FIR04-00769
| INSP-Final Inspection | 4/18/2005 | 4/18/2005 | 4/18/2005 12:00:00 AM | P | PASS |
|
|
fire alarm finaled
|