Inspections for the day of: Tuesday, April 18, 2006.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00254 FIR-Aging Inspection4/18/20064/18/20064/20/2006 12:43:47 PM DONE
No inspections have been requested to date.
FIR06-00211 INSP-Final Inspection4/18/20064/18/20064/18/2006 4:47:24 PMPNH
No access for inspection.
FIR05-00594 INSP-Final Inspection4/17/20064/18/20064/18/2006 4:45:48 PMPFAIL
Stairway sprinklers must be installed per NFPA 13 2002 8.14.3.2.1.
FIR06-00051 INSP-Final Inspection4/18/20064/18/20064/18/2006 4:38:11 PMPFAIL
Provide lockable supervision for the valves at the backflow prevention device, provide signage per fire code review notes at the BPD, the dry sidewall is installed in such a manner that does not prevent freezing of the supply pipe.
FIR05-00609 INSP-Final Inspection4/18/20064/18/20064/18/2006 3:25:39 PMPPASS
Fire alarm finaled.
FIR05-00052 INSP-Final Inspection4/18/20064/18/20064/18/2006 3:25:16 PMPPASS
Fire alarm passed final inspection, alarm permit finaled.
FIR05-00051 INSP-Final Inspection4/18/20064/18/20064/18/2006 3:24:39 PMPPASS
Fire alarm passed final inspection, permit finaled.
FIR04-00658 INSP-Final Inspection4/18/20064/18/20064/18/2006 3:23:48 PMPPASS
Corrections have been completed, inspection passed, permit finaled.
FIR04-00657 INSP-Final Inspection4/18/20064/18/20064/18/2006 3:22:52 PMPPASS
Corrections have been completed, inspection passed.
BLD05-02334 FIRE-Final Inspection4/17/20064/18/20064/18/2006 2:09:53 PMPNR
The project related alarm and sprinkler permits must be completed and approved prior to request for life safety final inspection.
FIR05-00712 INSP-Final Inspection4/17/20064/18/20064/18/2006 2:07:53 PMAPART
Resubmitted plans reflecting field changes verified, antifreeze tampers, co detectors, added SD, and mag locks at two locations in phase two tested okay. One set of door locks at phase 1 was not in condition to enable testing, fire doors at the second floor elevator phase 2 failed to operate due to closure adjustment issues. Updated map at the panel has been provided.
FIR05-00449 INSP-Alarm Testing4/17/20064/18/20064/18/2006 1:59:35 PMAPART
Elevator recall at floors 1-11 tested today, FD communication system intercom and phone jacks on floors 1-11 tested, voice evac re-tested on all floors, phase reversal monitoring for fire pump verified, added SD at lobby tested. Elevator machine room, elevator shutdown, main FACP, command center items per IFC, map at panel, and signal verification not inspected at this time.