ELE07-01298
| Conference | 4/17/2007 | 4/18/2007 | 4/18/2007 4:14:04 PM | P | DONE |
|
|
Bret pls call 30 min prior.; Phone #: ###-#### Internet Inspection Request from: Stacie Backus met owner, talked about service, u/g, sub-panel to house, grounding, chg range and dryer to 4-wire
|
ELE07-00728
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 3:50:25 PM | P | FAIL |
|
|
glenn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, nec 352.30(A) rnc shall be strapped within 3' of termination,110.22 each disconnect shall be legibly marked to show it's purpose, 410.8(A) edge of fixture shall be min 12" from edge of shelf
|
ELE07-00654
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 3:11:02 PM | P | FAIL |
|
|
glenn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, nec 110.22 each disconnect shall be legibly marked to indicate it's purpose,406.5 faceplates shall seat against mounting surface, 410.8(A) edge of fixture in closet shall be min 12" from edge of shelf
|
ELE07-01354
| Rough-In Permanent Service | 4/18/2007 | 4/18/2007 | 4/18/2007 2:29:32 PM | P | PASS |
|
|
daryl; Phone #: ###-#### Internet Inspection Request from: Victoria Beall p/s o/h rec ok
|
ELE07-00604
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 2:16:28 PM | P | FAIL |
|
|
glenn ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called, left corr notice, nec 406.4 recpts shall be securely fastened and mounted, 406.4(D) recpts shall be flush with or project from faceplates, 110.22 each disconnect shall be legibly marked to indicate it's purpose, 410.8(A) edge of fixture shall be min 12" from edge of shelf
|
ELE07-00946
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 1:43:47 PM | P | PASS |
|
|
RON - GARAGE; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
ELE06-03712
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 1:43:06 PM | P | PASS |
|
|
RON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
ELE07-00944
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 1:33:29 PM | P | PASS |
|
|
RON - GARAGE; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
ELE06-03713
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 1:32:49 PM | P | PASS |
|
|
RON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
ELE06-03886
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 1:05:02 PM | P | PASS |
|
|
RON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr ections made, ok to final
|
ELE07-00948
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 1:04:10 PM | P | PASS |
|
|
RON - GARAGE; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
ELE07-00947
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 12:49:58 PM | P | PASS |
|
|
RON - GARAGE; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
ELE06-04032
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 12:49:08 PM | P | PASS |
|
|
RON; Phone #: ###-#### Internet Inspection Request from: Victoria Beall corr made, ok to final
|
ELE07-01357
| Electrical Rough-In | 4/18/2007 | 4/18/2007 | 4/18/2007 11:07:38 AM | P | PASS |
|
|
Daryl; Phone #: ###-#### Internet Inspection Request from: Stacie Backus u/g ok to cover, see final
|
ELE07-01357
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 11:05:20 AM | P | PASS |
|
|
Daryl; Phone #: ###-#### Internet Inspection Request from: Stacie Backus ok to final, told elect not to hook uo because sign not listed
|
ELE07-00294
| Final | 4/17/2007 | 4/18/2007 | 4/18/2007 10:58:02 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Lynn Solmon ok to final
|
ELE07-00946
| Final | 4/17/2007 | 4/18/2007 | 4/18/2007 10:05:53 AM | A | FAIL |
|
|
Ron detached garage; Phone #: ###-#### Internet Inspection Request from: Stacie Backus see ele06-03712 for description
|
ELE07-00944
| Final | 4/18/2007 | 4/18/2007 | 4/18/2007 9:49:39 AM | A | FAIL |
|
|
see ele06-03713 for fail corr notice
|
ELE06-03712
| Final | 4/17/2007 | 4/18/2007 | 4/18/2007 9:47:43 AM | A | FAIL |
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 406.4 recpts shall be securely mounted, 406.4(D) recpts shall be flush with or project from faceplates, 110.3(B) listed equip shall be installed according to instructions-faceplate screws, 110.22 each disconnect shall be legibly marked to indicate it's purpose
|
ELE06-03713
| Final | 4/17/2007 | 4/18/2007 | 4/18/2007 9:34:34 AM | A | FAIL |
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 110.22 each disconnect shall be legibly marked to indicate it's purpose, 210.8(A) garage gfci shall operate-downstream, 406.4 receptacles shall be securely mounted, 408.4 circuit directory shall be clear, complete, concise and explanatory
|
ELE07-00948
| Final | 4/17/2007 | 4/18/2007 | 4/18/2007 9:02:03 AM | A | FAIL |
|
|
Ron detached garage; Phone #: ###-#### Internet Inspection Request from: Stacie Backus see ele06-03886 for correction
|
ELE06-03886
| Final | 4/17/2007 | 4/18/2007 | 4/18/2007 9:01:08 AM | A | FAIL |
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, 110.22 each disconnect shall be legibly marked to indicate its purpose, 406.4(D) recpts shall be flush with or project from it's faceplate, 110.3(B) listed equipment shall be installed inj accordance with instructions- switch plate screw, globe garage
|
ELE07-00947
| Final | 4/17/2007 | 4/18/2007 | 4/18/2007 8:19:44 AM | A | FAIL |
|
|
Ron detached garage; Phone #: ###-#### Internet Inspection Request from: Stacie Backus see fail for ele06-04032, disconnect marking nec 110.22
|
ELE06-04032
| Final | 4/17/2007 | 4/18/2007 | 4/18/2007 8:18:03 AM | A | FAIL |
|
|
Ron; Phone #: ###-#### Internet Inspection Request from: Stacie Backus called, left corr notice, nec 408.4 circuit directory shall be complete, clear, and concise, 406.4 receptacles shall be flush with or project from their faceplates, 110.22 each disconnect shall be legibly marked to indicate its purpose
|