FIR06-00657
| FIR-Aging Inspection | 4/18/2007 | 4/18/2007 | 4/25/2007 10:49:46 PM | | DONE |
|
|
Pending completion of one remaining area.
|
FIR07-00292
| INSP-Sprinkler Rough-in | 4/17/2007 | 4/18/2007 | 4/18/2007 3:53:28 PM | P | PART |
|
|
OH install is approved for cover at areas as red lined and initialed on stamped plans including the kitchen, two restrooms, and two dining rooms, noted armovers supplying drops with static system pressures in excess of 100 psi. to have hangers and surge restraint within 1' of the head, freezer DP are not installed at this time.
|
FIR07-00183
| INSP-Final Inspection | 4/18/2007 | 4/18/2007 | 4/18/2007 3:09:23 PM | P | FAIL |
|
|
Pendent head in the utility/storage room is obstructed by adjacent ductwork.
|
FIR06-00399
| INSP-Final Inspection | 4/18/2007 | 4/18/2007 | 4/18/2007 2:40:39 PM | P | PASS |
|
|
Fire alarm permit finaled.
|
FIR07-00126
| INSP-Final Inspection | 4/16/2007 | 4/18/2007 | 4/18/2007 2:10:14 PM | A | PASS |
|
|
Fire sprinkler work passed inspection, noted one head at an adjacent room to be removed as indicated on plans.
|
FIR07-00034
| INSP-Sprinkler Rough-in/Hydro | 4/17/2007 | 4/18/2007 | 4/18/2007 2:08:42 PM | A | PART |
|
|
1st floor OH rough-in is acceptable, noted flexible couplings are to be installed where pipe passes through non-frangible construction and no seismic clearance is provided, attatchment method at one lateral brace needs to be changed as the beam clamp used is not listed for this purpose.
|
BLD07-00138
| FIRE-Final Inspection | 4/17/2007 | 4/18/2007 | 4/18/2007 11:02:44 AM | A | PASS |
|
|
Corrections are complete, fire life safety passed inspection.
|
FIR06-00985
| INSP-Supply line flush | 4/17/2007 | 4/18/2007 | 4/18/2007 10:54:28 AM | A | PART |
|
|
UG fire supply line flush completed satisfactory at the west building riser, also approved garage areas for cover as corrections have been made.
|
FIR06-00595
| INSP-Alarm Testing | 4/17/2007 | 4/18/2007 | | P | |
|
|
don - after 5p, said he talked to forrest; Phone #: ###-#### Internet Inspection Request from: Victoria Beall
|