Inspections for the day of: Wednesday, April 18, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00536 INSP-Sprinkler Rough-in4/18/20074/18/20074/18/2007 4:38:55 PMPPASS
See city approved plans for areas on the eigth floor where the sprinkler piping is ok to cover.
BLD06-02369 FIRE-Final Inspection4/17/20074/18/20074/18/2007 4:37:56 PMPCANC
Need fire alarm and fire sprinkler permits finaled first
MIS07-00077 FIR-Final4/18/20074/18/20074/18/2007 4:37:07 PMPPASS
Life safety passed
FIR07-00171 INSP-Final Inspection4/18/20074/18/20074/18/2007 2:55:11 PMPFAIL
No approved plans on site, pull station is mounted too high. Phone lines and sprinkler devices were tested ok.
FIR07-00100 INSP-Final Inspection4/17/20074/18/20074/18/2007 2:49:22 PMPFAIL
Need drawings resubmitted as previously requested. Still need the hydro test performed. Also since the anti-freeze connection point has been relocated an additional flow switch is required.
FIR07-00264 INSP-Alarm Testing4/17/20074/18/20074/18/2007 2:17:22 PMPFAIL
Provide minumum 7.6 ah batteries, set up monitoring, provide flow switch for anti-freeze loop(may require resubmittals), relocate duct smoke detector, provide map at the facp, provide sticker for hvac reset and test al a/v's. See city approved plans for complete list.
FIR07-00171 INSP-Final Inspection4/18/20074/18/20074/18/2007 11:46:25 AMPCANC
Rafe phone; ###-#### Inspection cancelled from web by: Terry Owsley
BLD07-00246 FIRE-Final Inspection4/17/20074/18/20074/18/2007 11:09:35 AMAPASS
permit finaled
FIR07-00171 INSP-Final Inspection4/18/20074/18/20074/18/2007 10:50:34 AMPCANC
Rafe''s Phone Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley