Inspections for the day of: Friday, April 18, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Johnson
TitlePLM-INSPECTOR
Phone #794-9476
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM08-00011 Plumbing Rough-in4/17/20084/18/20084/18/2008 4:22:02 PMPCANC
Phone #: ###-#### Internet Inspection Request from: raul castanon
PLM08-00595 Final4/18/20084/18/20084/18/2008 3:36:53 PMPPART
troy Phone #: ###-#### need R P to dish washer need hot and cold R P to commerical washing machine need separate water supply to chemical dispenser by mop sink need three inch floor sink mim. for discharge from washing machine
PLM08-00571 Groundwork4/18/20084/18/20084/18/2008 3:27:12 PMPPASS
Scheduled by a contractor via Hello! on 4/18/2008 at 7:29:52 AM. Contact: ###-####.
PLM08-00877 Groundwork4/18/20084/18/20084/18/2008 2:28:31 PMPPASS
Call Darren please Phone #: ###-#### Internet Inspection Request from: joe paige
PLM07-01944 Plumbing Rough-in4/18/20084/18/20084/18/2008 2:04:50 PMPPASS
steve Phone #: ###-#### for up staires main bath rough-in only at this time
PLM08-00872 Water and/or Sewer4/18/20084/18/20084/18/2008 1:20:54 PMPFAIL
Bill Phone #: ###-#### neeed to uncover tie-in to meter stub for inspection unable to find a shut off or drain down valve need to have vented portion of R P 12 inches above finished grade need to have R P tested and certified called contractor will recall when ready left correction notice on site
PLM08-00803 Water and/or Sewer4/18/20084/18/20084/18/2008 12:58:40 PMPPASS
steve - also underground Phone #: ###-#### water, sewer and ground work test ok
PLM08-00443 Final4/17/20084/18/20084/18/2008 12:41:56 PMPPASS
Scheduled by a contractor via Hello! on 4/17/2008 at 5:02:32 PM. Contact: ###-####.
PLM08-00034 Plumbing Rough-in4/18/20084/18/20084/18/2008 12:18:17 PMPPASS
PLM08-00790 Water and/or Sewer4/17/20084/18/20084/18/2008 11:20:21 AMAFAIL
bw Phone #: ###-####-- call 1st before insp test failed on sewer line need to correct reverse grade in A B S need to cut out pvc 3034 fitting,s and repipe with approved glue need to add an additional clean out in 3034 pvc line over 135 degree turn contractor to recall when ready
PLM08-00825 Plumbing Rough-in4/17/20084/18/20084/18/2008 11:14:53 AMPCANC
this definately a rough-in inspection. sj Phone #: ###-#### Internet Inspection Request from: Erin Whiting plumbing rough-in was done on 4/16/2008
PLM08-00743 Plumbing Rough-in4/16/20084/18/20084/18/2008 9:43:13 AMACANC
Ready by 10:00AM Phone #: ###-#### Internet Inspection Request from: John Hensley
PLM08-00854 Water and/or Sewer4/17/20084/18/20084/18/2008 9:31:27 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom
PLM08-00854 DOC - Permit Finaled4/18/20084/18/20084/18/2008 9:31:14 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Scott Wickstrom
PLM08-00382 Final4/18/20084/18/20084/18/2008 9:22:20 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Brent Lacy
PLM08-00034 Plumbing Rough-in4/17/20084/18/20084/18/2008 8:55:37 AMAPART
Nate Sturlin is the field contact. Phone #: ###-#### Internet Inspection Request from: Heidi Mallet water system test ok still need to test roof and overflow drains and vent,s contractor to recall when ready
PLM08-00825 Final4/17/20084/18/20084/17/2008 12:41:15 PMACANC
Phone #: ###-#### Internet Inspection Request from: Erin Whiting Inspection cancelled from web by: Erin Whiting