Inspections for the day of: Friday, April 18, 2008.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD07-03162 FIRE-Final Inspection4/16/20084/18/20084/18/2008 10:34:38 AMACANC
jim - fire life safety Phone #: ###-####
FIR07-00697 INSP-Sprinkler Rough-in4/17/20084/18/20084/18/2008 10:17:02 AMAPART
Piping is ok to cover except near the cafeteria area due to vapor barrier contacting the upright sprinkler heads and in the classroom where the upright sprinkler heads are located too far from the deck. Also the two uprights at the attic access ladder are too far from the deck. Also the eaves are ok to cover. I let the general contractor know that nearly all of the manual pull stations for the fire alarm system are mounted too high and will need to be lowered.