BLD07-03162
| FIRE-Final Inspection | 4/16/2008 | 4/18/2008 | 4/18/2008 10:34:38 AM | A | CANC |
|
|
jim - fire life safety Phone #: ###-####
|
FIR07-00697
| INSP-Sprinkler Rough-in | 4/17/2008 | 4/18/2008 | 4/18/2008 10:17:02 AM | A | PART |
|
|
Piping is ok to cover except near the cafeteria area due to vapor barrier contacting the upright sprinkler heads and in the classroom where the upright sprinkler heads are located too far from the deck. Also the two uprights at the attic access ladder are too far from the deck. Also the eaves are ok to cover. I let the general contractor know that nearly all of the manual pull stations for the fire alarm system are mounted too high and will need to be lowered.
|