Inspections for the day of: Monday, April 18, 2016.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00242 INSP-Final Inspection4/15/20164/18/20164/19/2016 9:49:14 AMAFAIL
Need as-builts showing the correct location of the remote annunciator provided to Lee in plan review.
BLD16-00279 FIRE-Final Inspection4/15/20164/18/20164/18/2016 1:55:23 PMAPASS
Life safety passed. All items corrected. A sprinkler system analysis has been provided showing that Class 1 - 3 can be stored up to 20'. Per a discussion with Tim Frost and a review of the provided documentation it appears the the commodity is a Class IV which per NFPA 13 (see page 133) only allows a maximum storage height of 12'-0". On page 136 of NPFA 13 only a Class I will be allowed to be stored to 20'-0". So the maximum storage height allowed for the commodity stored will be 12'-0". All aisle widths to be a minimum of 44". I spoke to Greg McRoberts about these conditions. Side note: the previous product stored at 14'-0" has been reduced to 11'-0" at the time of inspection.
BLD16-01159 FIRE-Final Inspection4/15/20164/18/20164/18/2016 8:35:10 AMAPASS
life safety passed